| Plan Review Notes For Permit 02051282 |
| Permit Number |
02051282 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-05-29 00:00:00 | UNSAT! | | | ~~~~~~ | | | PLEASE COMPLY WITH THE FOLLOWING AND | | | RESUBMIT FOR REVIEW; | | | | | | 1} PLEASE SUBMIT AIC RATINGS FOR | | | ALL NEW EQUIPMENT BEING INSTALLED. | | | MAINS/PANELS/BREAKERS MUST BE RATED FOR | | | THE AVAILABLE FAULT CURRENT PER 110-9. | | | | | | 2} PLEASE SHOW ALL OUTLETS SERVING | | | KITCHEN COUNTERSPACE AS GFI/GFI | | | PROTECT--ED PER 210-8-A-6. | | | INCLUDES KITCHEN ISLANDS. | | | | | | 3} PLEASE LIST THE REQ'D BATH(S) | | | CIRCUIT(S). PER 210-11-C-3 | | | MUST BE 20A AND #12AWG. | | | | | | 4} PLEASE LIST THE REQ`D ARC | | | FAULT PROECTED CIRCUITS ON PANEL | | | SCHEDULE. PER 210-12. | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/659-8096 EXT. 8392 |
|