| Plan Review Notes For Permit 02051229 |
| Permit Number |
02051229 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-06-07 00:00:00 | DENIED | | | REFERENCE: FBC-2001 CHAPTER 11 | | | FBC-2001 PLUMBING | | | | | | 1) TABLE 403.1 REQUIRES 1 DRINKING FOUN- | | | TAIN AND 1 SERVICE SINK. | | | 2) PLEASE SUBMIT DETAIL ON BREAK ROOM | | | SINK. MUST COMPLY WITH 11-4.24. | | | 3) SHOW HOW RELIEF VALVE DISCHARGE AND | | | PAN DRAIN SHALL BE PIPED. 504.7.1 & | | | 504.8.1/504.8.2 | | | 4) WALLS OF ALL PUBLIC REST ROOMS SHALL | | | BE LINED WITH NON ABSORBENT MATERIAL TO | | | A HEIGHT OF 4'. FBC SEC 1204.2 | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 |
|