Plan Review Notes
Plan Review Notes For Permit 02051229
Permit Number 02051229
Review Stop P
Sequence Number 1
Notes
Date Text
2002-06-07 00:00:00DENIED
 REFERENCE: FBC-2001 CHAPTER 11
 FBC-2001 PLUMBING
  
 1) TABLE 403.1 REQUIRES 1 DRINKING FOUN-
 TAIN AND 1 SERVICE SINK.
 2) PLEASE SUBMIT DETAIL ON BREAK ROOM
 SINK. MUST COMPLY WITH 11-4.24.
 3) SHOW HOW RELIEF VALVE DISCHARGE AND
 PAN DRAIN SHALL BE PIPED. 504.7.1 &
 504.8.1/504.8.2
 4) WALLS OF ALL PUBLIC REST ROOMS SHALL
 BE LINED WITH NON ABSORBENT MATERIAL TO
 A HEIGHT OF 4'. FBC SEC 1204.2
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377