| Plan Review Notes For Permit 02051150 |
| Permit Number |
02051150 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-05-28 00:00:00 | MECHANICAL PERMIT 02051151 | | | | | | PLEASE NOTE - NO FIRE DAMPERS ARE | | | INDICATED ON PLANS (EXISTING OR NEW). | | | ARCHITECTERIAL DRAWINGS WERE NOT | | | SUBMITTED.COULD NO DETERMINE IF ANY | | | OF THE CORRIDOR WALLS, MECHANICAL ROOMS | | | OR STORAGE ROOMS HAVE A FIRE RESISTANT | | | RATING.FIRE DAMPERS NEW OR EXISTING | | | SHALL BE LOCATED ON THE PLANS AS PER | | | 2001 FBC(M) 607.6. | | | | | | PLEASE INDICATE ALL DUCT SMOKE DETECTORS | | | ON THE PLAN. | | | | | | PLEASE INDICATE CONDENSATE LINE SIZE AND | | | DISPOSAL LOCATION. 2001 FBC(M) 307.2.1. |
|