| Notes |
| Date |
Text |
| 2002-06-05 00:00:00 | MECHANICAL PERMIT 02051138 | | | | | | PLAN INDICATES 1650 CFM AIR | | | DISTRIBUSTION & THE EQUIPMENT SCHEDULE | | | INDICATES 1950 CFM, PLEASE CORRELATE. | | | PLEASE NOTE AS PER 2001 FBC(M) 606.2.1, | | | SMOKE DETECTORS SHALL BE INSTALLED IN | | | SUPPLY AIR SYSTEMS WITH A DESIGN | | | CAPACITY GREATER THAN 2,000 CFM. | | | | | | CONDENSATE SHALL DISCHARGE A MINIMUM OF | | | 12" AWAY FROM THE BUILDING STRUCTURE AS | | | PER 2001 FBC 1503.4.4. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|