2002-05-23 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 659 8096 EXT 8499
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
  
 1) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) THE PERMIT APPLICATION FORM GIVES
 225 CLEMATIS ST AS THE ADDRESS WHICH IS
 NOT CONSISTENT WITH THE 221-223 CLEMATIS
 ST ADDRESS ON THE PLANS.PROVIDE THE
 CORRECT ADDRESS.
  
 3) FBC 503.1.2AREA LIMITATIONS.THE
 PLANS SHALL STATE THE OCCUPANCY
 CLASSIFICATION AS EITHER LARGE ASSEMBLY
 OR SMALL ASSEMBLY (FBC 304.2), WHETHER
 THE BUILDING IS SPRINKLERED, THE TYPE OF
 CONSTRUCTION (FBC 601) AND THUS WHETHER
 THE PROPOSED OCCUPANCY COMPLIES WITH THE
 ALLOWABLE BUILDING AREA AS PER TABLE 500
  
 4) FBC 903.7.2.4SPRINKLERS.IF EITHER
 OF THE OCCUPANCIES IS NOT SPRINKLERED,
 THE PROPOSED INCREASE IN OCCUPANT LOAD
 MAY NECESSITATE PROTECTION BY AN APPROVE
 D AUTOMATIC SPRINKLER SYSTEM.THE PLANS
 SHALL STATE THE CURRENT AND PROPOSED
 OCCUPANCY LOADS AND WHETHER SPRINKLERED.
  
 5) THE PLANS SHOW LINTELS OVER THE
 ARCHED OPENINGS ONLY.AMEND THE PLANS
 TO SHOW LINTELS OVER THE GLAZED OPENINGS
  
 6) FBC* 104.2.1.2ONE OF THE NEW
 GLAZED OPENINGS IS SHOWN TO ABUTT AN
 EXISTING COLUMN.SUBMIT A DETAIL OF THE
 LINTEL BEARING AT THIS LOCATION.
  
 7) PROVISO:
 FBC 2405THE TEMPERED GLASS IN THE NEW
 OPENINGS SHALL BE IN ACCORDANCE WITH THE
 REQUIREMENTS OF CPSC 16-CFR, PART 1201.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 IF YOU HAVE ANY QUESTIONS PLEASE CALL:
 ROBERT BROWN(561) 659 8096 EXT 8499