| 2002-05-23 00:00:00 | BUILDING PLAN REVIEW |
| | *******DENIED******* |
| | ROBERT BROWN(561) 659 8096 EXT 8499 |
| | |
| | FBC = FLORIDA BUILDING CODE 2001 |
| | FBC*= FLORIDA BUILD'G CODE (CITY AMEND) |
| | |
| | 1) A RECORDED COPY OF THE NOTICE OF |
| | COMMENCEMENT MUST BE SUBMITTED BEFORE A |
| | PERMIT CAN BE ISSUED. |
| | |
| | 2) THE PERMIT APPLICATION FORM GIVES |
| | 225 CLEMATIS ST AS THE ADDRESS WHICH IS |
| | NOT CONSISTENT WITH THE 221-223 CLEMATIS |
| | ST ADDRESS ON THE PLANS.PROVIDE THE |
| | CORRECT ADDRESS. |
| | |
| | 3) FBC 503.1.2AREA LIMITATIONS.THE |
| | PLANS SHALL STATE THE OCCUPANCY |
| | CLASSIFICATION AS EITHER LARGE ASSEMBLY |
| | OR SMALL ASSEMBLY (FBC 304.2), WHETHER |
| | THE BUILDING IS SPRINKLERED, THE TYPE OF |
| | CONSTRUCTION (FBC 601) AND THUS WHETHER |
| | THE PROPOSED OCCUPANCY COMPLIES WITH THE |
| | ALLOWABLE BUILDING AREA AS PER TABLE 500 |
| | |
| | 4) FBC 903.7.2.4SPRINKLERS.IF EITHER |
| | OF THE OCCUPANCIES IS NOT SPRINKLERED, |
| | THE PROPOSED INCREASE IN OCCUPANT LOAD |
| | MAY NECESSITATE PROTECTION BY AN APPROVE |
| | D AUTOMATIC SPRINKLER SYSTEM.THE PLANS |
| | SHALL STATE THE CURRENT AND PROPOSED |
| | OCCUPANCY LOADS AND WHETHER SPRINKLERED. |
| | |
| | 5) THE PLANS SHOW LINTELS OVER THE |
| | ARCHED OPENINGS ONLY.AMEND THE PLANS |
| | TO SHOW LINTELS OVER THE GLAZED OPENINGS |
| | |
| | 6) FBC* 104.2.1.2ONE OF THE NEW |
| | GLAZED OPENINGS IS SHOWN TO ABUTT AN |
| | EXISTING COLUMN.SUBMIT A DETAIL OF THE |
| | LINTEL BEARING AT THIS LOCATION. |
| | |
| | 7) PROVISO: |
| | FBC 2405THE TEMPERED GLASS IN THE NEW |
| | OPENINGS SHALL BE IN ACCORDANCE WITH THE |
| | REQUIREMENTS OF CPSC 16-CFR, PART 1201. |
| | |
| | **QUOTE PERMIT# ON ALL CORRESPONDENCE** |
| | |
| | END OF REVIEW COMMENTS |
| | THE CODE REFERENCES GIVE ADDITIONAL INFO |
| | IF YOU HAVE ANY QUESTIONS PLEASE CALL: |
| | ROBERT BROWN(561) 659 8096 EXT 8499 |