Plan Review Notes
Plan Review Notes For Permit 02051066
Permit Number 02051066
Review Stop M
Sequence Number 1
Notes
Date Text
2002-05-20 00:00:00PROVISO:
  
 1.PLAN SHEET A9 DETAIL 8, EXHAUST DUCT
 FIRE SHIELDING - SHOULD VARIATION #1
 BE USED PLEASE PROVIDE MANUFACTURERS
 INSTALLATION INSTRUCTIONS PRIOR TO
 INSTALLATION.
  
 2.PLEASE NOTE ALL WELDS ARE TO BE
 INSPECTED PRIOR TO COVERING.
  
 3.EF-2 SHALL ALSO BE A HINGED UPBLAST
 (SEE DETAIL ON PLAN SHEET M5) AS
 PER NFPA 96 4-8.2.1(E).
  
 4.10 FT MINIMUM FROM ANY ADJACENT
 BUILDING, PARKING AREA, ADJACENT
 PROPERTY LINE, WINDOW, DOOR OR AIR
 INTAKE OPENING. 1997 SMC 506.1.
  
 5.AIR VELOCITY WITHIN THE DUCT SYSTEM
 SHALL NOT BE LESS THAN 1,500 FT PER
 MINUTE AS PER 1997 SMC 505.7 & NFPA
 96 5-2.1.
  
 PLEASE NOTE SEPARATE PERMIT REQUIRED
 FOR FIRE SUPRESSION.PLEASE PROVIDE
 PLANS WITH PERMIT APPLICATION.
  