| Notes |
| Date |
Text |
| 2002-05-24 00:00:00 | 1) PLEASE PROVIDE PRODUCT APPROVALS FOR | | | ONE HOUR FIRE SHIELDING DISPLAYED ON | | | THE PLANS. | | | | | | 2) A MINIMUM OF 10 FEET FROM ANY | | | ADJACENT BUILDING, PARKING AREA, | | | ADJACENT PROPERTY LINE, WINDOW, DOOR, | | | OR AIR INTAKE. | | | | | | 3) SEPARATE PLANS AND PERMITS REQUIRED | | | FOR HOOD,DUCT,AND EXTINGUISHING SYSTEM. | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 659-8096,EXT.8497 | | | 835-2910 |
|