| 2002-05-29 00:00:00 | UNSAT! |
| | ~~~~~~ |
| | PLEASE PROVIDE THE FOLLOWING |
| | INFORMATION-MAKE ALL NECESSARY CHANGES |
| | ON PLANS,AND RESUMBIT FOR REVIEW. |
| | |
| | 1} PLEASE SUBMIT AIC RATINGS FOR |
| | ALL NEW EQUIPMENT BEING INSTALLED. |
| | MAINS/PANELS/BREAKERS MUST BE RATED FOR |
| | THE AVAILABLE FAULT CURRENT PER 110-9. |
| | |
| | 2} INDICATE CONDUIT & WIRE SIZES AND |
| | TYPES FROM THE MAIN DISCONNECT TO ALL |
| | PANELS AND DISCONNECTS BEING FED. |
| | |
| | 3} THE 60 AMP SUB PANEL IN THE GARAGE |
| | MUST COMPLY WITH 225-31 & |
| | 225-32,DISCONNECTING AND 250-32 |
| | GROUNDING PROVISIONS. |
| | |
| | 4} INDICATE THE TYPE GROUNDING SYSTEM |
| | AND SIZE OF THE ELECTRODE CONDUCTOR |
| | BEING USED AT THE MAIN DISCONNECT PER |
| | 250-50 & 250-66. |
| | |
| | 5} INDICATE THE SIZE OF THE OVERCURRENT |
| | PROTECTION AND AMPERAGE RATING OF THE |
| | MAIN DISCONNECT. |
| | |
| | 6} PLEASE LIST THE REQ'D ARC |
| | FAULT PROTECTED CIRCUITS ON PANEL |
| | SCHEDULE, PER 210-12.NOTE ALL |
| | DESIGNATED SLEEPING AREAS ARE REQUIRED |
| | TO HAVE SAME. |
| | |
| | 7} ALL SLEEPING AREAS MUST COMPLY 2-2.1. |
| | 1.1 NFPA-72,AND INTERCONNECTED PER2-2.2. |
| | 1. |
| | |
| | 8} NOTE THE A/C IS LISTED ON A 60 AMP |
| | BREAKER ON THE PANEL SCHEDULE AND SHOWN |
| | AS 6K IN THE LOAD CALCS.,PLEASE CLARIFY. |
| | |
| | 9} THE CALCULATION USED FOR DETERMINING |
| | THE LOAD FOR THIS RESIDENCE SHOULD BE |
| | MADE BY COMPILING A GENERAL LOAD WITH |
| | DEMAND FACTORS OR FROM ARTICLE 220-30. |
| | |
| | 10} THE GROUND SHOWN AT THE 200 AMP |
| | PANEL MUST BE REMOVED PER 250-24(A)(1). |
| | |
| | BILL TROBAUGH |
| | ELECTRICAL PLAN REVIEW |