| 2002-08-14 00:00:00 | DENIED:2ND REQUEST | | | | | | 1.PLEASE PROVIDE INFORMATION ON A/C | | | EQUIPMENT TO BE INSTALLED. | | | | | | 2.SEER ON THE ENERGY CALCS INDICATE | | | 9.70.FLA ENERGY CODE REQUIRES NO | | | LESS THAN A 10 SER ON A SPLIT | | | SYSTEM.9.70 IS PERMITTED FOR A | | | PACKAGE UNIT.PLEASE CLARIFY WHAT | | | TYPE OF EQUIPMENT IS TO BE INSTALLED | | | 2001 FBC CHAPTER 13 TABLE 6-3. | | | | | | REF:PAGE 6A - "APPLICATION ENGINEERING | | | FOR HEATING & COOLING" HVAC SYSTEM | | | TYPE:OVERHEAD FURNACE.IS THIS | | | THE EQUIPMENT FOR THE A/C SYSTEM? | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|