Plan Review Notes
Plan Review Notes For Permit 02051028
Permit Number 02051028
Review Stop B
Sequence Number 1
Notes
Date Text
2002-06-14 00:00:00BUILDING PLAN REVIEW
 PERMIT: 02051028
 ADD: 801 GRANT ST
 CONT: PLAN REVIEW
 TEL: (561)835-1989
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 1) PROVIDE 2 CURRENT COPIES OF SIGNED &
 SEALED SURVEYS WITH PROPOSED IMPROVEMENT
 TO BE COMPLETED.
  
 2) FL BLD CODE 1804.2.2 QUESTIONABLE
 SOILS, WHERE THE BEARING CAPACITY IS
 NOT DEFINETLY KNOWN OR IS IN QUESTION.
  
 3) FOUNDATION DETAIL TO BE USED 9-D,E&F
 THIS IS A GENERIC DETAIL, IT IS TO BE
 SITE SPECIFIC, TO MEET CODE REQUIREMENTS
 FOR STEM WALL CONSTRUCTION. HEIGTH;
 A) FL BLDG 1804.1.3 THE BOTTOM OF THE
 FOUNDATION SHALL EXTEND NO LESS THAN
 12" BELOW FINISHED GRADE.
 B) FL BLDG 2304.3.3 WHEN WOOD JOIST
 OR THE BOTTOM OF WOOD STRUCTURAL FLOORS
 WITHOUT JOIST ARE CLOSER THAN 18",THEN A
 PPROVED NATURALLY DURABLE WOOD OR
 PRESSURE TREATED WOOD IS TO BE USED.
  
 3)-FL BLDG 1012.1.5 LANDINGS:
 IN GROUP R-3 OCCUPANCIES, LANDINGS MAY
 BE ONE STEP LOWER THAN INSIDE FLOOR
 LEVEL, BUT NO MORE THAN 7". LANDINGS
 SHALL NOT BE LESS THAN THE DOR IT SERVES
 AND NOT LESS THAN 36".
  
 4) THE STATE CERTIFIED PLANS INDICATE
 THAT THE INSTALLATION INSTRUCTIONS, FOR
 ADDITIONAL SET UP INFORMATION,ALSO INFOR
 MATION ON GLAZING PROTECTION FOR WIND-
 BORNE DEBRIS REFIONS, FL BLDG CODE
 1606.1.4 REQUIRES PROTECTION OF ALL
 GLAZED OPENINGS,PLEASE PROVIDE MISSING
 INFORMATION PACKET PAGES 1-36.
 THE STATE HAS APPROVED THE USE OF
 WOOD STRUCTURAL PANELS FOR PROTECTION OF
 GLAZED OPENINGS, BUT TO 130 MPH, SEE
 TABLE 1606.1.4 NOTE# 1.
  
 5) THIS SAME INFORMATION PACKAGE HAS
 INFORMATION ON THE HINGED ROOF.
  
 6) FL ENERGY SHEET INDICATES 3 DIFFERENT
 ZONES, NORTH, CENTER & SOUTHERN ZONES,
 ITEM # 5 IS THIS WORST CASE? ANSWER NO.
 CHECKING WITH DCA TO SEE WHY THIS WAS
 NOT THE WORST CASE, IF THIS WAS MASTERED
 THROUGH THE STATE? OR IF THIS SHOULD BE
 SITE SPECIFIC? THE STATE INDICATED BY
 RETURN PHONE CALL (ILLA JONES) THAT IF
 THE STATE CERTIFICATION WAS NOT FOR FOR
 THE WORST CASE FOR EACH ZONE, THEN SITE
 SPECIFIC ENERGY CALCS SHALL BE REQUIRED.
  
 7) CHAP 13 TABLE 6-3, ELECTRICALLY
 DRIVEN COOLING EQUIPMENT, CAPACITIES
 < 65,000 BTU/H MINIMUM PERFORMANCE
 LEVELS CENTRAL UNITS MINIMUM SEER 10.0.
 ENERGY CALC INDICATE 9.7?????
  
 LOOK FOR COMMENTS BY THE OTHER PLAN
 REVIEW DISCIPLINES THAT MAY BE WRITTEN
 ON THE APPLICATION, PLANS, OR ATTACHED
 SEPARATELY. WHEN RESUBMITTING PLANS
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A
 DESCRIPTION OF THE REVISION MADE, IDEN-
 TIFYING THE SHEET OR SPECIFICATION PAGE
 WHERE THE CHANGES CAN BE FOUND, WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION.
 JIM WITMER
 PLAN REVIEW
 TEL: (561)659-8096 EX.8412
 FAX: (561)659-8026


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved