| Plan Review Notes For Permit 02051002 |
| Permit Number |
02051002 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-06-07 00:00:00 | DENIED | | | REFERENCE: FBC-2001 424.2 SWIMMING POOLS | | | | | | A) PLEASE ADJUST YOUR NOTES, DETAILS, OR | | | SUBMITTALS TO REFLECT THE FOLLOWING IN- | | | FORMATION REQUIRED FOR PLAN REVIEW | | | 1) FBC-2001424.2.6.6.2 SHOW COMPLIANCE | | | WITH ANSI/ASME A112.19.8M. PROVIDE MODEL | | | NUMBER AND MANUF INFO FOR VAC LOCK. | | | (GIVE DETAIL OR ADD NOTE)(SUBMITTAL) | | | 2) FBC-2001424.2.6.6.5 WHERE PROVIDED, | | | THE VACUUM OR PRESSURE CLEANER FITTING | | | SHALL BE LOCATED AT LEAST 6" AND NOT | | | GREATER THAN 12" BELOW THE MINIMUM OPER- | | | ATING WATER LEVEL OR AS AN ATTACHMENT TO | | | THE SKIMMER. | | | 3) FBC-2001 424.2.14.2 WATER RETENTION, | | | PROVIDE A POSITIVE MEANS OF RETAINING | | | WATER IN THE HEATER WHEN PUMP IS SHUT | | | OFF. (MANUFACTURE CUT SHEETS SUBMITTAL) | | | 4) FBC-2001 424.2.14.4 CONNECTIONS, ALL | | | WATER HEATING EQUIPMENT SHALL BE INSTAL- | | | LED WITH FLANGES OR UNION CONNECTIONS | | | ADJACENT TO THE HEATER. (ADD TO NOTES) | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 |
|