| Plan Review Notes For Permit 02051001 |
| Permit Number |
02051001 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-05-21 00:00:00 | UNSAT! | | | ~~~~~~ | | | 1} PLEASE SUBMIT AIC RATINGS FOR | | | ALL NEW EQUIPMENT BEING INSTALLED. | | | MAINS/PANELS/BREAKERS MUST BE RATED FOR | | | THE AVAILABLE FAULT CURRENT PER 110-9. | | | | | | 2} PLEASE INDICATE THE SIZE AND TYPE OF | | | THE SERVICE ENTRANCE CONDUCTORS IN THE | | | RISER,ALSO IN THE NIPPLE TO THE | | | DISCONNECT. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | 561/659-8096 EXT. 88392 |
|