2002-06-03 00:00:00DENIED:
 1. PROVIDE LOCATION AND DESIGN
 INFORMATION ON FIRE DAMPERS AT RATED
 WALLS.
  
 2. FAN SHUT DOWN BY DUCT SMOKE DETECTOR
 REQUIRED FOR ALL SYSTEMS WITH GREATER
 THAN 2000 CFM.
  
 3. ARCHITECTURAL DRAWINGS ARE NOT SIGNED
 AND SEALED
  
 4 PROVIDE ENGINEERING ON CURB ATTACHMENT
 TO ROOF MEETING THE REQUIRED WIND LOAD
 RATING.