| Plan Review Notes For Permit 02050999 |
| Permit Number |
02050999 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-06-03 00:00:00 | DENIED: | | | 1. PROVIDE LOCATION AND DESIGN | | | INFORMATION ON FIRE DAMPERS AT RATED | | | WALLS. | | | | | | 2. FAN SHUT DOWN BY DUCT SMOKE DETECTOR | | | REQUIRED FOR ALL SYSTEMS WITH GREATER | | | THAN 2000 CFM. | | | | | | 3. ARCHITECTURAL DRAWINGS ARE NOT SIGNED | | | AND SEALED | | | | | | 4 PROVIDE ENGINEERING ON CURB ATTACHMENT | | | TO ROOF MEETING THE REQUIRED WIND LOAD | | | RATING. |
|