| Plan Review Notes For Permit 02050855 |
| Permit Number |
02050855 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-05-17 00:00:00 | 1) CLEARANCES TO FIRE HYDRANTS MUST BE | | | AT LEAST SEVEN AND HALF FEET TO THE | | | FRONT AND SIDES OF THEM. FOUR FEET | | | CLEARANCE IS TO BE PROVIDED TO THE | | | REAR OF THEM. RE: FFPC 3-5.6.2.1 | | | | | | 2) THE ABOVE CLEARANCES ARE TO BE | | | PROVIDED TO FIRE PROTECTION APPLIANCES. | | | | | | 3) APPROPRIATE SIGNAGE IS TO BE PROVIDED | | | "NO PARKING, FIRE DEPARTMENT CONNECTION" | | | IN ACCORDANCE WITH DOT STANDARDS FOR | | | INFORMATION SIGNAGE. RE: FFPC 3-5.6.2.3 | | | | | | 4) ELECTRONIC SWITCHES WILL BE REQUIRED | | | ON FIRE LINE BACKFLOW DEVICES. | | | | | | 5) WET FIRE HDYRANTS ARE REQUIRED PRIOR | | | TO, DURING AND AFTER CONSTRUCTION. | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 659-8096,EXT.8497 | | | 835-2910 |
|