| Plan Review Notes For Permit 02050850 |
| Permit Number |
02050850 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-06-03 00:00:00 | **************** UNSAT ***************** | | | | | | 1)NOTE: PLEASE CLARIFY OUTLET (GFI) | | | OUTLET FOR GARAGE. PER 210-52G SHOWN | | | AS WATER HEATER?? | | | | | | 2)NOTE: PLEASE MISSING RECEPT FOR COND | | | UNITS. | | | | | | 3)NOTE: PLEASE CLARIFY POOL LIGHTS SHOWN | | | AS 20A ON #14 AWG. PLEASE CORRELATE | | | OCP WITH CORRECT AWG. | | | | | | 4)NOTE: PLEASE LIST THE REQ`D ARC FAULT | | | PROTECTION ON PANEL SCHEDULE. PER 210-12 | | | | | | 5)NOTE: PLEASE NOTE MISSING OUTLET FOR | | | MASTER BEDROOM HALLWAY. PER 210-52H | | | | | | 6)NOTE: PLEASE NOTE THAT ON THE BOTTOM | | | OF LOAD CALCULATIONS, SHOWS KW/.24V? | | | MISPRINT? | | | | | | PLEASE SUBMIT THE ABOVE FOR REVIEW. | | | IF THERE ARE ANY QUESTIONS,PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|