| 2002-06-17 00:00:00 | CHECKLIST: |
| | 1-NEED RECORDED NOTICE OF COMMENCEMENT. |
| | 2-ENTRY DOOR DOESN'T PROVIDE 32" MIN. |
| | CLEAR OPENING REQUIRED BY TABLE 1004 |
| | FBC 2001. REVISE AS REQUIRED. |
| | 3-FLOOR PLANS & ELEVATIONS DON'T MATCH. |
| | 4-WINDOW AT ENTRY AREA EXCEEDS THE MAX. |
| | PERCENTAGE OF OPENING ALLOWED BY TABLE |
| | 600 FBC 2001. REVISE AS REQUIRED. |
| | 5-SPECIFY FIREBLOCKING MATERIALS AND |
| | LOCATION AT STAIRS. SEC. 2305.1.4 FBC |
| | 6-SPECIFY DRAFSTOPPING LOCATION AND |
| | MATERIAL AT 2ND FL. FRAMING PLAN AS |
| | REQUIRED BY SECTION 2305.2.2 FBC 2001. |
| | 7-SPECIFY FIRE CUTS AT MASONRY WALL AS |
| | REQUIRED BY SECTION 2305.4 FBC 2001. |
| | 8-PROVIDE SPECIFICATIONS FOR SOIL AND |
| | FOOTING PROTECTION WHEN IMPACT OF |
| | WATER FROM ROOF VALLEYS. SEE SECTION |
| | 1804.1.6 FBC 2001. |
| | 9-PROVIDE SOIL TEST REPORT. |
| | 10-DESIGN JOINTS AT CONCRETE SLAB OR |
| | SPECIFY SUPPORTS FOR WWM. SEE SECTION |
| | 1909.3 FBC 2001. |
| | 11-STORM SHUTTERS: |
| | A)PROVIDE COMPLETE INSTALLATION SCHEDULE |
| | & KEY PLAN. SEE ATTACHED CITY SAMPLE. |
| | B)CLEARLY INDICATE ON DRAWINGS SPECIFIC |
| | MOUNTING CONDITIONS AND ANCHOR TYPE |
| | AND SPACING TO BE USED ACCORDING TO |
| | THE DESIGN PRESSURES, EDGE DISTANCE, |
| | MEAN ROOF HEIGHT, CONNECTION TYPE, |
| | PANEL SPAN & STRUCTURE TO BE ATTACHED |
| | TO. |
| | 12-PROVIDE PRODUCT APPROVAL FOR DOUBLE |
| | ENTRY DOORS (NO SIDELITES) AS SHOWN ON |
| | PLANS. PRODUCT APPROVAL SUBMITTED IS |
| | SINGLE DOOR ONLY. |