| Notes |
| Date |
Text |
| 2002-06-27 00:00:00 | *************** UNSAT ***************** | | | | | | 1)NOTE: PLEASE NOTE THAT MAIN ELECTRICAL | | | ROOM LAYOUT SHOWS "NEW DISC" AT 200A | | | FROM BUS DUCT, PLEASE NOTE THAT RISER | | | DIAGRAM SHOWS AS 100A W/ 70A FUSES? | | | PLEASE CLARIFY WHICH ONE. | | | | | | 2)NOTE: PLEASE INDICATE GFI/GFI PROTECT- | | | ION FOR OUTLETS IN BREAK ROOM. PER | | | LOCAL AMENDMENTS 210-8 | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|