Plan Review Notes
Plan Review Notes For Permit 02050711
Permit Number 02050711
Review Stop R
Sequence Number 1
Notes
Date Text
2002-06-26 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 659 8096 EXT 8499
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
  
 1) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) SHEET A-1.0L, GENERAL NOTE 2.AMEND
 REFERENCE FROM STANDARD BUILDING CODE TO
 FLORIDA BUILDING CODE 2001
  
 3) SHEET A-1.0L, GENERAL NOTES. A NUMBER
 OF THE ASTM AND ACI PUBLICATION
 REFERENCES GIVEN ARE NOW OUT OF DATE.
 UPDATE GENERAL NOTES.
  
 4) SHEET S5, GENERAL NOTE 3.CHANGE
 AMENDMENT REFERENCE FROM PALM BEACH
 COUNTY TO CITY OF WEST PALM BEACH
 AMENDMENTS.
  
 5) ASCE 7-98 6.5.6.1SHEET S1 AND TRUSS
 LAYOUT PLAN.THE EXPOSURE CATEGORY FOR
 DETERMINING WIND LOADS AT THIS LOCATION
 IS CATEGORY B NOT C.
  
 6) ASCE 7-98 FIG.6-1BSHEET S2, ROOF
 FRAMING NOTE 3.THE WIND VELOCITY FOR
 THIS LOCATION IS 140MPH NOT 110MPH.
  
 7) SHEET S3, TRUSS ANCHOR SCHEDULE.
 PRODUCT CODE HTA18 IS NOT A VALID USP
 REFERENCE.RE-SPECIFY THESE ANCHORS.
  
 8) SHEET S2, TRUSS CONNECTION TO GIRDER
 TRUSS.DETAIL 5/S2 REFERS TO DETAIL
 9/S2 WHICH IS NOT SHOWN.PROVIDE A
 CONNECTION DETAIL AT THIS LOCATION.
  
 9) FBC 1007.5.1 & FBC 1015AMEND THE
 PLANS TO DEMONSTRATE COMPLIANCE WITH THE
 REQUIREMENTS FOR STAIRCASE HANDRAILS AND
 GUARDING.
  
 10) FBC 1005.4.4EGRESS WINDOWS.ADD
 DIMENSIONS TO THE PLANS TO DEMONSTRATE
 COMPLIANCE WITH THE REQUIREMENT FOR A
 MINIMUM CLEAR EGRESS OPENING HEIGHT OF
 24 INCHES.
  
 11) GEOTECHNICAL REPORT.UNDER THE
 HEADING 'ADDITIONAL EXPLORATIONS' (FINAL
 PAGE OF TEXT), ARDAMAN AND ASSOCIATES
 RECOMMEND TWO AUGER BORINGS AT EACH
 BUILDING PAD BEFORE EXCAVATION OF
 FOOTINGS.SHOW THAT THIS RECOMMENDATION
 HAS BEEN ADDRESSED.
  
 12) FBC 1606THE POSITIVE AND NEGATIVE
 WIND LOAD PRESSURES FOR THE SKYLIGHT
 SHALL BE STATED ON THE PLANS FOR
 CROSS REFERENCE WITH THE PRODUCT
 APPROVAL.
  
 13) FBC 1606.1.4SKYLIGHT.THE
 SUBMITTED MIAMI-DADE PRODUCT CONTROL
 NOTICE OF ACCEPTANCE NO. 99-0326.13, FOR
 THE SKYLIGHT, EXPIRED BEFORE THE PERMIT
 APPLICATION WAS SUBMITTED.SUBMIT A
 VALID PRODUCT APPRVAL.
  
 14) GARAGE DOOR PRODUCT APPROVAL.THE
 SUBMITTED EVALUATION REPORT DRAWING IS
 FOR A MAXIMUM DOOR WIDTH OF 9'-0" WHICH
 IS LESS THAN THE GARAGE DOOR WIDTH SHOWN
 ON ARCHITECTURAL SHEET A-1.0L.SUBMIT A
 RELEVANT PRODUCT APPROVAL DRAWING.
  
 15) PRODUCT APPROVAL FOR KDI WINDOWS.
 THE DRAWINGS THAT SHOULD ACCOMPANY
 SBCCI EVALUATION REPORT 9733A WERE NOT
 SUBMITTED. SUBMIT THE RELEVANT DRAWINGS,
 FOR THE WINDOWS AND SLIDING GLASS DOORS.
 DRAWINGS WERE SUBMITTED WITH A COPY OF
 SUPERCEDED REPORT 9733, BUT THOSE
 NUMBERED 96-101, 97-002 AND 97-003 ARE
 NOT LEGIBLE AND THE VALIDITY OF THESE
 DRAWINGS CANNOT BE ESTABLISHED.
  
 16) SINGLE HUNG WINDOWS AT BREAKFAST
 AREA AND BEDROOM 3.SBCCI EVALUATION
 REPORT 9733A.THE POSITIVE DESIGN WIND
 PRESSURE STATED ON THE PLANS EXCEEDS THE
 ALLOWABLE WIND PRESSURE IN TABLE 1 OF
 THE EVALUATION REPORT, FOR THE KDI
 SINGLE HUNG WINDOW.SUBMIT A PRODUCT
 APPROVAL FOR A WINDOW WITH SUFFICIENT
 WIND LOAD CAPACITY.
  
 17) ENTRANCE DOOR WITH SIDELIGHT.A
 NUMBER OF DIFFERENT PRODUCT APPROVALS
 HAVE BEEN SUBMITTED.ONLY ONE INCLUDES
 SIDELIGHTS BUT IT ALSO REQUIRES THE
 INSTALLATION OF HURRICANE SHUTTERS.
 CLARIFY WHICH PRODUCTS ARE TO BE USED
 FOR THE ENTRANCE AND THE MEANS OF
 HURRICANE MISSILE IMPACT PROTECTION.
  
 18) WINDOW MULLION/TRANSOM.KD WINDOWS,
 INC. DRAWING NO. 1013 SHEETS 1 TO 3 OF 3
 HAVE BEEN SUBMITTED WITHOUT ANY PRODUCT
 APPROVAL OR EVALUATION REPORT.SUBMIT A
 COMPLETE PRODUCT APPROVAL FOR THE
 TRANSOM ABOVE THE GREAT ROOM SLIDING
 GLASS DOORS.
  
 19) THE SUBMITTED HURRICANE MISSILE
 IMPACT PROTECTION SHUTTER INSTALLATION
 SCHEDULE AND KEY PLAN ARE FOR A
 DIFFERENT ADDRESS AND LOT NUMBER.
 SUBMIT A RELEVANT SCHEDULE AND KEY PLAN.
  
 20) ROOF TILE.THE SUBMITTED PRODUCT
 CONTROL NOTICE OF ACCEPTANCE #98-0717.01
 FOR THE ENTEGRA "ESTATE" ROOFING TILE
 EXPIRED BEFORE THE PERMIT APPLICATION
 WAS SUBMITTED.SUBMIT A VALID PRODUCT
 APPROVAL.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 IF YOU HAVE ANY QUESTIONS PLEASE CALL:
 ROBERT BROWN(561) 659 8096 EXT 8499