2002-06-03 00:00:00*************** UNSAT *****************
  
 1)NOTE: PLEASE LIST THE REQ`D ARC FAULT
 PROTECTION ON PANEL SCHEDULE PER 210-12
  
 2)NOTE : PLEASE SEE 250-66 FOR SIZING
 OF GROUNDING ELECTRODE CONDUCTOR.
  
 3)NOTE: PLEASE NOTE OVEN SHOWN ON PANEL
 SCHEDULE BUT NOT SHOWN IN LOAD
 CALCULATIONS?? PLEASE SHOW.
  
 4)NOTE: PLEASE NOTE WASHER SHOWN AS
 3KW ON LOAD CALCULATIONS AND ONLY SHOWN
 ON A 20A #12 ON PANEL SCHEDULE.
  
 5)NOTE: PLEASE NOTE OCP FOR 10KW AHU
 TO BE AT 125% PER 424-3B
  
 PLEASE SUBMIT THE ABOVE FOR REVIEW.
 IF THERE ARE ANY QUESTIONS,PLEASE CALL.
  
 DEWEY PALMER