| Notes |
| Date |
Text |
| 2002-06-03 00:00:00 | *************** UNSAT ***************** | | | | | | 1)NOTE: PLEASE LIST THE REQ`D ARC FAULT | | | PROTECTION ON PANEL SCHEDULE PER 210-12 | | | | | | 2)NOTE : PLEASE SEE 250-66 FOR SIZING | | | OF GROUNDING ELECTRODE CONDUCTOR. | | | | | | 3)NOTE: PLEASE NOTE OVEN SHOWN ON PANEL | | | SCHEDULE BUT NOT SHOWN IN LOAD | | | CALCULATIONS?? PLEASE SHOW. | | | | | | 4)NOTE: PLEASE NOTE WASHER SHOWN AS | | | 3KW ON LOAD CALCULATIONS AND ONLY SHOWN | | | ON A 20A #12 ON PANEL SCHEDULE. | | | | | | 5)NOTE: PLEASE NOTE OCP FOR 10KW AHU | | | TO BE AT 125% PER 424-3B | | | | | | PLEASE SUBMIT THE ABOVE FOR REVIEW. | | | IF THERE ARE ANY QUESTIONS,PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|