| Plan Review Notes For Permit 02050710 |
| Permit Number |
02050710 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2002-07-10 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | | | | 1) SHT E-1.0R TUB AND SHOWER ARE NOT | | | VENTED IN MASTER BATH. 2ND NOTICE. THE | | | WET VENT SHALL BE CONSIDERED THE VENT | | | FOR THE FIXTURES AND SHALL ENTEND FROM | | | THE CONNECTION OF THE DRY VENT ALONG THE | | | DIRECTION OF THE FLOW IN THE DRAIN PIPE | | | TO THE MOST DOWNSTREAM FIXTURE DRAIN | | | CONNECTION TO THE HORIZONTAL BRANCH | | | DRAIN. SECTION 909.1 | | | 2) SHT E-1.0R PLUMBING NOTES #7 CHANGE | | | TO READ WATER HAMMER ARRESTORS, NOT | | | WATER CHAMBERS ARRESTORS. | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 |
|