| Date |
Text |
| 2002-06-13 00:00:00 | BUILDING DENIED |
| | |
| | 1) IMPACT FEES MUST BE PAID TO PALM |
| | BEACH COUNTY, PLANS STAMPED BY THEM AND |
| | COPY OF RECEIPT SUBMITTED TO CITY OF |
| | WEST PALM BEACH BUILDING DEPARTMENT, |
| | BEFORE A BUILDING PERMIT CAN BE ISSUED. |
| | |
| | 2) FBC* 104.2.5SITE SURVEY.A SIGNED |
| | AND SEALED SURVEY DRAWING PREPARED BY A |
| | QUALIFIED SURVEYOR IS REQUIRED. |
| | |
| | 3) SURVEY IS NEEDED IN ORDER TO REVIEW |
| | PLAN FOR COMPLIANCE WITH FBC TABLE 600 |
| | FOR PERCENT OF WALL AREA ALLOWED AS |
| | OPENINGS. |
| | |
| | 4) PLEASE CHANGE NOTE #2 ON A1 TO REFER |
| | TO 2001 FLORIDA BUILDING CODE. |
| | |
| | 5) PLEASE CHANGE NOTE #1 ON S5 UNDER |
| | SAFEGUARDS TO REFERENCE THE FBC. |
| | |
| | 6) PLEASE INDICATE ON SHEET A4 THAT THE |
| | STUCCO APPLIED VERTICALLY ON METAL LATHE |
| | OVER A SOLID BASE IS REQUIRED TO BE 7/8" |
| | THICK PER FBC SEC. 2504.2 AND ASTM C-926 |
| | |
| | 7) PLEASE INDICATE ON THE PLANS THAT |
| | ADEQUATE SUBSTRATE WILL BE PROVIDED FOR |
| | THE ATTACHMENT OF THE STORM PANELS. |
| | |
| | 8) PLEASE CORRECT DETAIL 1 ON S3, WHICH |
| | INDICATES 3/16" HOLES FOR THE 3/4" BOLTS |
| | |
| | 9) PLEASE CORRECT THE FOLLOWING NOTES ON |
| | ON SHEET A5: |
| | - NOTE #5 UNDER ROOF SHEATHING REFERS TO |
| | SBC |
| | - NOTE #1 UNDER REINFORCED CONCRETE |
| | REFERS TO THE SBC. NOTE #7 REFERS TO |
| | ASTM A-185 AND IT SHOULD BE ASTM A-185. |
| | THE NOTES STATE THAT WWF SHOULD BE |
| | LIFTED DURING CONCRETE PLACEMENT, THE |
| | FBC SEC. 1909.3 REQUIRES THE WELDED WIRE |
| | FABRIC TO BE SUPPORTED. |
| | |
| | 10)PLEASE CORRECT THE DESIGN INFORMATION |
| | GIVEN ON SHEET S1. THE EXPOSURE |
| | CATEGORY FOR LARKSPUR LANDING IS B, THE |
| | IMPORTANCE FACTOR IS 1.00, THE ASCE |
| | TABLE FOR DETERMINING THE IMPORTANCE |
| | FACTOR IS 6-1 IN ASCE7-98. PLEASE |
| | INDICATE THE INTERNAL PRESSURE |
| | COEFFICIENT ( + OR - .18 FOR ENCLOSED). |
| | THE 2001 FBC SECTION 1606.1.7 |
| | REQUIRES THE FOLLOWING INFORMATION TO BE |
| | SHOWN ON THE CONSTRUCTION DRAWINGS: |
| | - BASIC WIND SPEED, MPH. |
| | - WIND IMPORTANCE FACTOR(1) AND BUILDING |
| | CATEGORY. |
| | - WIND EXPOSURE- IF MORE THAN ONE WIND |
| | EXPOSURE IS USED THE WIND EXPOSURE AND |
| | APPLICABLE WIND DIRECTION SHALL BE |
| | INDICATED. |
| | - THE APPLICABLE INTERNAL PRESSURE |
| | COEFFICIENT |
| | - COMPONENTS AND CLADDING. THE DESIGN |
| | WIND PRESSURES IN TERMS OF PSF, TO BE |
| | USED FOR THE DESIGN OF EXTERIOR |
| | COMPONENT AND CLADDING MATERIALS NOT |
| | SPECIFICALLY DESIGNED BY THE REGISTERED |
| | DESIGN PROFESSIONAL. |
| | |
| | 11) THE CALCULATED WINDLOAD PRESSURES |
| | FOR THE SINGLE HUNG WINDOWS AND SLIDING |
| | GLASS DOOR GIVEN ON THE PLANS EXCEEDS |
| | THE DESIGN PRESSURES LISTED IN THE SBCCI |
| | PRODUCT APPROVAL FOR KDI WINDOWS AND THE |
| | COMPARATIVE ANALYSIS SUBMITTED IS NOT A |
| | VALID DOCUMENT. |
| | |
| | 12) PROVIDE (2) CURRENT AND COMPLETE |
| | COPIES OF SBCCI OR METRO-DADE PRODUCT |
| | APPROVALS FOR: |
| | - STRUCTURAL MULLIONS |
| | - ROOF TILE ; THE PRODUCT APPROVALS FOR |
| | THE ENTEGRA ROOF TILE EXPIRED PRIOR TO |
| | DATE OF SUBMITTAL |
| | |
| | 13) PROVIDE KEY PLAN AND INSTALLATION |
| | SCHEDULE FOR THESE PLANS (MODEL E). |
| | |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |
| | (561)659-8096 EXT.8202 |