Text |
| 2002-05-25 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | | | | 1) SHT E-1.0 R, TUB AND SHOWER ARE NOT | | | VENTED IN MASTER BATH. | | | 2) SHT E-1.0 R, PLUMBING NOTES #7, AIR | | | CHAMBERS ARE NOT APPROVED. CHANGE NOTE | | | TO READ WATER HAMMER ARRESTORS ARE RE- | | | QUIRED FOR ALL QUICK CLOSING VALVES, | | | (W/M - D/W - & ICE MAKER). | | | 3) SHT E-1.0 R. PLUMBING NOTES #4, CON- | | | DENSATE SHALL DISCHARGE MINIMUM OF 12" | | | FROM BLDG. FBC-2001 SEC 1503.4.4 | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 |
|