Plan Review Notes
Plan Review Notes For Permit 02050710
Permit Number 02050710
Review Stop E
Sequence Number 1
Notes
Date Text
2002-06-03 00:00:00**************** UNSAT *****************
  
 1)NOTE: PLEASE LIST THE REQ`D ARC FAULT
 PROTECTION ON PANEL SCHEDULE PER 210-12.
  
 2)NOTE: PLEASE NOTE OCP FOR AHU TO BE
 SIZED AT 125% OF 10KW. PER 424-3B
  
 3)NOTE: PLEASE NOTE SIZING OF GROUNDING
 ELECTRODE CONDUCTOR PER 250-66.
  
 4)NOTE : PLEASE NOTE WASHER SHOWN AS
 3KW ON LOAD CALCULATIONS AND THEN SHOWN
 ON A 20A CIRCUIT ON PANEL SCHEDULE??
 PLEASE CLARIFY.
  
 5)NOTE: PLEASE NOTE THAT OVEN IS SHOWN
 ON PANEL SCHEDULE AND IS NOT SHOWN ON
 LOAD CALCULATIONS.??
  
 6)NOTE: PLEASE NOTE MISSING SD OUTSIDE
 MASTER BEDROOM PER NFPA-72 2-2.1.1.1
  
 7)NOTE: PLEASE NOTE PLACENMENT OF MASTER
 BATH RECEPT PER 210-52D.
 NEED TO ADD ONE OR MOVE EXISTING..
  
 PLEASE SUBMIT THE ABOVE FOR REVIEW.
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372