| Plan Review Notes For Permit 02050710 |
| Permit Number |
02050710 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-06-03 00:00:00 | **************** UNSAT ***************** | | | | | | 1)NOTE: PLEASE LIST THE REQ`D ARC FAULT | | | PROTECTION ON PANEL SCHEDULE PER 210-12. | | | | | | 2)NOTE: PLEASE NOTE OCP FOR AHU TO BE | | | SIZED AT 125% OF 10KW. PER 424-3B | | | | | | 3)NOTE: PLEASE NOTE SIZING OF GROUNDING | | | ELECTRODE CONDUCTOR PER 250-66. | | | | | | 4)NOTE : PLEASE NOTE WASHER SHOWN AS | | | 3KW ON LOAD CALCULATIONS AND THEN SHOWN | | | ON A 20A CIRCUIT ON PANEL SCHEDULE?? | | | PLEASE CLARIFY. | | | | | | 5)NOTE: PLEASE NOTE THAT OVEN IS SHOWN | | | ON PANEL SCHEDULE AND IS NOT SHOWN ON | | | LOAD CALCULATIONS.?? | | | | | | 6)NOTE: PLEASE NOTE MISSING SD OUTSIDE | | | MASTER BEDROOM PER NFPA-72 2-2.1.1.1 | | | | | | 7)NOTE: PLEASE NOTE PLACENMENT OF MASTER | | | BATH RECEPT PER 210-52D. | | | NEED TO ADD ONE OR MOVE EXISTING.. | | | | | | PLEASE SUBMIT THE ABOVE FOR REVIEW. | | | IF THERE ARE ANY QUESTIONS, PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|