| 2002-05-23 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 424.2 SWIMMING POOLS |
| | |
| | A) PLEASE ADJUST YOUR NOTES, DETAILS, OR |
| | SUBMITTALS TO REFLECT THE FOLLOWING IN- |
| | FORMATION REQUIRED FOR PLAN REVIEW. |
| | 1) COMPLY WITH FBC-2001 SEC 424.2 |
| | PRIVATE SWIMMING POOLS. |
| | 2) FBC-2001 SEC 424.2.6.1 ENGINEERING |
| | DESIGN, CONSTRUCTION AND WORKMANSHIP. |
| | ANSI/NSPI-4 92. AND NSPI-5 |
| | 4) FBC-2001 SEC 424.2.6.6 ENTRAPMENT |
| | PROTECTION FOR SUCTION INLETS. (DETAIL) |
| | 5) FBC-2001424.2.6.6.2 SHOW COMPLIANCE |
| | WITH ANSI/ASME A112.19.8M. PROVIDE MODEL |
| | NUMBER AND MANUF INFO FOR VAC LOCK IF |
| | VACUUM LINE. (DETAIL/NOTE/OR SUBMITTAL) |
| | 6) VENT - VENT SHALL BE VENTED TO ATMOS- |
| | PHERE IN A MANNER THAT THE VENT WILL NOT |
| | BE BLOCKED BY INFESTATION, DEBRIS BUILD |
| | UP, OR MICROBIOLOGICAL CONTAMINATION. |
| | LABLE VENT: "POOL SAFETY DEVICE- DO NOT |
| | HANDLE. (ADD TO NOTES) |
| | 7) FBC-2001 424.2.7.2 PUMPS AND EQUIP- |
| | MENT SHALL BE MOUNTED ON A SUBSTANTIAL |
| | BASE IN A MANNER THAT WILL ELIMINATE |
| | STRAIN ON PIPING. SLAB SHALL BE A NOMIN- |
| | AL 4" THICK. (DETAIL) |
| | 8) FBC-2001 424.2.9 WATER SUPPLY, LOCAL |
| | ORD. #2853-95, BACKFLOW REQUIRED ON |
| | WATER SERVICE. (ADD TO NOTES) |
| | 9) FBC-2001 424.2.12.1 PRESSURE TESTS. |
| | PER MANUFACTURE RECOMMENDATIONS, NO AIR |
| | TEST SHALL BE APPROVED FOR PVC PIPE AND |
| | FITTINGS. (ADD TO NOTES) |
| | 1O) FBC-2001 424.2.13.2JOINTS AND CON- |
| | NECTIONS, FBC PLMG SEC 605.21, PURPLE |
| | PRIMER REQUIRED ON PVC PIPING. (ADD TO |
| | NOTES) |
| | 11) ALL SHEETS OF A SIGNED AND SEALED |
| | SET OF PLANS SHALL BE SIGNED AND SEALED. |
| | 8-1/2" X 11" SHEET WITH TITLE BLOCK NOT |
| | SEALED AND DATED. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 659-8096 EXT 8377 |