Plan Review Notes
Plan Review Notes For Permit 02050585
Permit Number 02050585
Review Stop E
Sequence Number 2
Notes
Date Text
2002-09-26 00:00:00UNSAT
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
  
 PLEASE PROVIDE THE FOLLOWING
 INFORMATION AND MAKE ANY NECESSARY
 CHANGES ON THE PLAN.
  
 1} PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
  
 2} INDICATE THE LOCATION OF THE NEW
 PANEL ON THE PLANS.
  
 3} PLEASE LIST THE REQ'D ARC
 FAULT PROTECTED CIRCUITS ON PANEL
 SCHEDULE OR NOTE ON PLANS FOR BRANCH
 CIRCUIT PROTECTION. PER 210-12.THE
 FLORIDA ROOM COULD BE CONVERTED INTO A
 SLEEPING ROOM.THE SMOKE DETECTORS MEET
 THE INTENT OF NFPA-72,BUT NOTE THE
 LOCATION OF THE ONE OUTSIDE THE
 BATHROOM MUST COMPLY WITH 8-1.4.2.(3'
 AWAY FROM THE DOOR).
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL;
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 561/659-8096 EXT. 8392