Plan Review Notes
Plan Review Notes For Permit 02050585
Permit Number 02050585
Review Stop B
Sequence Number 1
Notes
Date Text
2002-06-11 00:00:00 
 BUILDING PLAN REVIEW
 PERMIT: 02050585
 ADD: 941 44TH ST
 CONT: O/B DOUGLAS, ESTELLA
 TEL:848-0633
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 1)FL BLDG 1909.3 (EXEPTION# 2)
 CONCRETE SLABS ON GRADE CONTAINING 6X6/
 W1.4XW1.4 WELDED WIRE REINFORCEMENT
 FABRIC LOCATED IN THE MIDDLE TO THE
 UPPER 1/3RD OF THE SLAB SHALL BE SUP-
 PORTED BY APPROVED MATERIALS OR SUPPORTS
 AT SPACING NOT TO EXCEED 3 FT OR IN
 ACCORDANCE WITH MANUFACTURER'S SPEC.
  
 2)FIGURE 1606 WIND-BORNE DEBRIS
 REGION; INDICATES THAT W.P.B. CITY OF IS
 LOCATED IN THE 140 MPH ZONE. PLANS ARE
 TO INDICATE THIS. PLANS WERE DESIGNED
 UNDER 130MPH, HANDWRITTEN IS 140MPH,
 NO NOTE FROM THE DESIGN PROFESSIONAL
 THAT IS INITIALED NOR SEALED LETTER.
  
 3)PROVIDE (2) CURRENT AND COMPLETE
 COPIES OF SBCCI OR METRO-DADE PRODUCT
 APPROVALS FOR:
 A) WINDOWS
 B) DOORS
 C) ROOFING MATERIALS
 D) STORM SHUTTERS
 E) MULLIONS
  
 4)1707.4.5.1 MULLIONS OCCURRING
 BETWEEN INDIVIDUAL WINDOW AND GLASS
 DOOR ASSEMBLIES. TESTING REPORTS ARE
 REQUIRED BY AN APPROVED TESTING
 LABORATORY OR BE ENGINEERED.
  
 5)1707.4.5.2 MULLIONS SHALL BE DESIGN-
 ED TO TRANSFER THE DESIGN PRESSURE LOADS
 APPLIED BY THE WINDOW OR DOOR ASSEMBLIES
 TO THE ROUGH OPENING SUBTRATE.
  
 6) DISCREPANCY:NORTH ELE. MISSING THE
 BATHROOM WINDOW.
  
 7) FL BLD CODE CHAP 13 ENERGY EFFICENCY
 PROVIDE ENERGY CALS/ W MANUAL "J"
  
 8) BEFORE A PERMIT TO CONSTRUCT CAN BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM
 BEACH CO.,THE PERMIT PLANS STAMPED BY
 THEM AND THE RECEIPT ATTACHED TO THE
 PERMIT APPLICATION.
  
 ANY QUESTIONS PLEASE CALL,
 JIM WITMER
 BUILDING PLAN REVIEW
 DEPARTMENT OF CONSTRUCTION SERVICES
 CITY OF WEST PALM BEACH
 (561) 659-8096 EXT. 8412