Plan Review Notes
Plan Review Notes For Permit 02050573
Permit Number 02050573
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2002-05-10 00:00:001) WET FIRE HYDRANTS ARE REQUIRED PRIOR
 TO, DURING AND AFTER CONSTRUCTION.
  
 2) CLEARANCES TO FIRE HYDRANTS MUST BE
 AT LEAST SEVEN FEET SIX INCHES TO THE
 FRONT AND SIDES OF THEM. A MINIMUM OF
 FOUR FEET IS TO BE PROVIDED TO THE REAR
 OF THEM.
  
 3) FIRE HYDRANTS SHALL BE SPACED BETWEEN
 300-500 FEET APART.
  
 4) ALL DEAD-END ROADS IN EXCESS OF 150
 FEET SHALL HAVE APPROVED TURN-AROUNDS
 50 FEET OF CENTERLINE.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497