| 2002-05-31 00:00:00 | *******************DENIED*************** | | | | | | 1.INDICATE OVERFLOW PROTECTION AS PER | | | 2001 FBC(M) 307.2.4, WHERE AN | | | AUXILIARY DRAIN PAN CANNOT BE | | | INSTALLED UNITER UNITS, A DRAIN PIPE | | | SHALL BE CONNECTED TO THE SECONDARY | | | DRAIN (OVERFLOW) CONNECTION.THE | | | OVERLOW CONDENSATE SHALL TERMINATE | | | AT A CONSPICUOUS POINT TO SERVE AS | | | AN ALARM WHICH INDICATES THAT THE | | | PRIMARY DRAIN IS RESTRICTED.PLEASE | | | INDICATE ON PLAN. | | | | | | 2.PRIMARY CONDENSATE SHALL DISCHARGE | | | A MINIMUM OF 12" AWAY FROM THE | | | BUILDING STRUCTURE AS PER 2001 FBC | | | 1503.4.4. | | | | | | 3.PLEASE PROVIDE OUTSIDE AIR CALCS AS | | | PER 2001 FBC(M) TABLE 403.3 - 20 CFM | | | PER PERSON. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|