Plan Review Notes
Plan Review Notes For Permit 02050537
Permit Number 02050537
Review Stop B
Sequence Number 1
Notes
Date Text
2002-05-22 00:00:00THIS IS A CHANGE OF OCCUPANCY USE AND
 MAY BE SUBJECT TO IMPACT FEES COLLECTED
 BY THE COUNTY.THE PERMIT PLANS MUST
 BE STAMPED BY THAT OFFICE AND A COPY OF
 THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION.CALL 561-233-5025 FOR
 MORE INFORMATION.
  
 SHOW THE METHOD OF HURRICANE MISSILE
 IMPACT RESISTANCE FOR THE EXTERIOR
 GLAZED AREAS PROPOSED TO BE INSTALLED.
 IF ALL OR THE INFORMATION IS NOT
 INCLUDED WITH THIS PERMIT APPLICATION,
 (PRODUCT APPROVALS, TEST REPORTS), A
 SEPARATE PERMIT AND FEES AND WILL BE
 REQUIRED.
  
 PLEASE PROVIDE A BASIC LIFE SAFETY PLAN
 SO THAT CODE COMPLIANCE FOR A GROUP D
 OCCUPANCY MAY BE DETERMINED.SHOW THE
 EXITS, EXIT DISCHARGE, SEATING AND
 FURNITURE PLANS, ETC.SEE FBC 1028.2.1
 AND 1010.
  
 SHOW EXISTING TOILET FACILITIES OR
 PROVISIONS FOR NEW, TO COMPLY WITH FBC
 1204 AND FBC 11-1.
  
 IS THE AREA SHOWN AS "LINE OF STORAGE
 ABOVE" SEPARATED FROM THE DAYCARE AREA
 IN ACCORDANCE WITH FBC 418.6?IF NOT
 PROVEIDE PLANS TO MODIFY AS NECASSARY.
 IS THIS AREA ACCESSED BY THE STAIR
 SHOWN TO BE SEPARTED UNDER THIS PERMIT?
 IF NOT WHAT IS THE AREA ACCESSED BY
 THE STAIR USED FOR?
  
 SHOW THE EXISTING OR PROVIDE NEW, THE
 FIRE AND SMOKE ALARMS IN ACCORDANCE
 WITH FBC 418.7.