Plan Review Notes
Plan Review Notes For Permit 02050463
Permit Number 02050463
Review Stop E
Sequence Number 2
Notes
Date Text
2002-05-22 00:00:00************ UNSAT ********************
  
 1)NOTE: PLEASE SHOW ALL EXISTING
 ELECTRICAL FOR HOUSE. PLEASE NOTE
 BRINGING SD`S UP TO CODE INSIDE AND
 OUTSIDE ALL EXISTING BEDROOMS ALSO PER
 NFPA-72 2-2.1.1.1.
  
  
 2)) NOTE: PLEASE NOTE FRONT AND REAR
 RECEPTS REQ`D PER 210-52E
  
 3 NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
  
 4) NOTE: PLEASE LIST THE REQ`D BATH(S)
 CIRCUIT(S). PER 210-11-C-3
 MUST BE 20A AND #12AWG.
  
 5 )NOTE: PLEASE LIST THE REQ`D ARC
 FAULT PROTECTED CIRCUITS ON PANEL
 SCHEDULE. PER 210-12
  
 6)NOTE: PLEASE NOTE OUTLET SPACING FOR
 KITCHEN COUNTERSPACE AND PENINSULAR.
 210-52-C-1,2,3,4,5
  
 7)NOTE: PLEASE NOTE OCP SHOWN FOR AHU`S
 NEEDS TO MEET 424-3B
  
 8)NOTE: PLEASE NOTE OTHER OCP SIZES
 EXCEED MAX 150% OCP FOR WATER HEATER AND
 DRYER. PLEASE VERIFY LOAD SHOWN FOR
 DRYER, SHOWN AS 4KW(UNCOMMON LOAD)??
  
 9)NOTE: PLEASE SHOW ON RISER DIAGRAM
 FOOTER STEEL AS SHOWN ON NOTE#7.
  
 10)NOTE: PLEASE SHOW SECOND AHU ON PLANS
  
 11)NOTE: PLEASE SHOW SERVICE LOCATION
 ON PLANS/PANEL/METER/.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE NAY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372