| 2002-05-22 00:00:00 | ************ UNSAT ******************** |
| | |
| | 1)NOTE: PLEASE SHOW ALL EXISTING |
| | ELECTRICAL FOR HOUSE. PLEASE NOTE |
| | BRINGING SD`S UP TO CODE INSIDE AND |
| | OUTSIDE ALL EXISTING BEDROOMS ALSO PER |
| | NFPA-72 2-2.1.1.1. |
| | |
| | |
| | 2)) NOTE: PLEASE NOTE FRONT AND REAR |
| | RECEPTS REQ`D PER 210-52E |
| | |
| | 3 NOTE: PLEASE SUBMIT AIC RATINGS FOR |
| | ALL NEW EQUIPMENT BEING INSTALLED. |
| | MAINS/PANELS/BREAKERS MUST BE RATED FOR |
| | THE AVAILABLE FAULT CURRENT PER 110-9. |
| | |
| | 4) NOTE: PLEASE LIST THE REQ`D BATH(S) |
| | CIRCUIT(S). PER 210-11-C-3 |
| | MUST BE 20A AND #12AWG. |
| | |
| | 5 )NOTE: PLEASE LIST THE REQ`D ARC |
| | FAULT PROTECTED CIRCUITS ON PANEL |
| | SCHEDULE. PER 210-12 |
| | |
| | 6)NOTE: PLEASE NOTE OUTLET SPACING FOR |
| | KITCHEN COUNTERSPACE AND PENINSULAR. |
| | 210-52-C-1,2,3,4,5 |
| | |
| | 7)NOTE: PLEASE NOTE OCP SHOWN FOR AHU`S |
| | NEEDS TO MEET 424-3B |
| | |
| | 8)NOTE: PLEASE NOTE OTHER OCP SIZES |
| | EXCEED MAX 150% OCP FOR WATER HEATER AND |
| | DRYER. PLEASE VERIFY LOAD SHOWN FOR |
| | DRYER, SHOWN AS 4KW(UNCOMMON LOAD)?? |
| | |
| | 9)NOTE: PLEASE SHOW ON RISER DIAGRAM |
| | FOOTER STEEL AS SHOWN ON NOTE#7. |
| | |
| | 10)NOTE: PLEASE SHOW SECOND AHU ON PLANS |
| | |
| | 11)NOTE: PLEASE SHOW SERVICE LOCATION |
| | ON PLANS/PANEL/METER/. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE NAY QUESTIONS, |
| | PLEASE CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-659-8096 EXT 8372 |