Plan Review Notes
Plan Review Notes For Permit 02050463
Permit Number 02050463
Review Stop B
Sequence Number 2
Notes
Date Text
2002-06-24 00:00:00APPROVED WITH PROVISO:
 1-THERE ARE TWO DIFFERENT GABLE END
 DETAILS. SEE SHEET A6 & A7. PROVIDE
 ONLY ONE DETAIL AND SPECIFY ALL
 STRUCTURAL MEMBERS AND ALL FASTENERS.
 **PROVIDE DIAGRAM AND CALCULATIONS
 SHOWING HOW IS GABLE END CONTINUOUS IN
 ORDER TO COMPLY WITH SECTION 2313.4.1
 FBC 2001.
 2-ARCHITECT TO PROVIDE ALL MINIMUM.
 INFORMATION REQUIRED ON DRAWINGS. SEE
 SECTION 1606.1.7 FBC 2001 FOR MINIMUM
 INFORMATION REQUIRED TO BE ON PLANS.
 3-SECTION A- A6 DOESN'T MATCH ENGINEERED
 TRUSS INFORMATION SUBMITTED. THESE ARE
 TWO COMPLETE DIFFERENT STRUCTURAL
 CONCEPTS.
 **ARCHITECT TO SPECIFY CONNECTORS OF
 TRUSS TO THE STRUCTURE.
 4-ARCHITECT TO SPECIFY HOW IS CONTINUOUS
 SUPPORT PROVIDED FOR GABLE END TRUSS @
 GABLE END TRUSS LOCATED ABOVE KITCHEN
 AREA. ALSO, SPECIFY ALL CONNECTORS.
 5-SPECIFY HOW ARE NEW TRUSSES ATTACHED
 TO EXISTING ROOF.
 6-PROVIDE COMPLETE ENGINEERED TRUSS
 PACKAGE WITH ORIGINAL SIGNATURE, SEAL
 AND DATE AS REQUIRED BY CHAPTER 471
 FLORIDA STATUTES.
 **NOTE: ARCHITECT TO REVIEW ALL TRUSS
 DRAWINGS (USE REVIEW STAMP) PRIOR TO
 SUBMITTAL.
2002-06-22 00:00:00 
 1-ARCHITECT TO PROVIDE COMPLETE DETAIL/
 SPECS FOR ANCHORING GABLE END TRUSS
 THAT IS SITUATED BETWEEN EXISTING