| 2002-06-24 00:00:00 | APPROVED WITH PROVISO: |
| | 1-THERE ARE TWO DIFFERENT GABLE END |
| | DETAILS. SEE SHEET A6 & A7. PROVIDE |
| | ONLY ONE DETAIL AND SPECIFY ALL |
| | STRUCTURAL MEMBERS AND ALL FASTENERS. |
| | **PROVIDE DIAGRAM AND CALCULATIONS |
| | SHOWING HOW IS GABLE END CONTINUOUS IN |
| | ORDER TO COMPLY WITH SECTION 2313.4.1 |
| | FBC 2001. |
| | 2-ARCHITECT TO PROVIDE ALL MINIMUM. |
| | INFORMATION REQUIRED ON DRAWINGS. SEE |
| | SECTION 1606.1.7 FBC 2001 FOR MINIMUM |
| | INFORMATION REQUIRED TO BE ON PLANS. |
| | 3-SECTION A- A6 DOESN'T MATCH ENGINEERED |
| | TRUSS INFORMATION SUBMITTED. THESE ARE |
| | TWO COMPLETE DIFFERENT STRUCTURAL |
| | CONCEPTS. |
| | **ARCHITECT TO SPECIFY CONNECTORS OF |
| | TRUSS TO THE STRUCTURE. |
| | 4-ARCHITECT TO SPECIFY HOW IS CONTINUOUS |
| | SUPPORT PROVIDED FOR GABLE END TRUSS @ |
| | GABLE END TRUSS LOCATED ABOVE KITCHEN |
| | AREA. ALSO, SPECIFY ALL CONNECTORS. |
| | 5-SPECIFY HOW ARE NEW TRUSSES ATTACHED |
| | TO EXISTING ROOF. |
| | 6-PROVIDE COMPLETE ENGINEERED TRUSS |
| | PACKAGE WITH ORIGINAL SIGNATURE, SEAL |
| | AND DATE AS REQUIRED BY CHAPTER 471 |
| | FLORIDA STATUTES. |
| | **NOTE: ARCHITECT TO REVIEW ALL TRUSS |
| | DRAWINGS (USE REVIEW STAMP) PRIOR TO |
| | SUBMITTAL. |
| 2002-06-22 00:00:00 | |
| | 1-ARCHITECT TO PROVIDE COMPLETE DETAIL/ |
| | SPECS FOR ANCHORING GABLE END TRUSS |
| | THAT IS SITUATED BETWEEN EXISTING |