| Plan Review Notes For Permit 02050452 |
| Permit Number |
02050452 |
|
| Review Stop |
FS |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2002-06-13 00:00:00 | 1) FIRE SPRINKLER HEADS ARE TO BE | | | LOCATED IN THE CENTER OF THE TILE. | | | | | | 2) THE ENTIRE INSTALLATION IS TO | | | BE DONE IN QUALITY MANNER APPROVED BY | | | THE FIRE RESCUE DEPARTMENT. | | | | | | 3) THE BUILDINGS WET FIRE DEPARTMENT | | | CONNECTION IS TO BE POSITIONED SO WHEN | | | FIRE HOSE IS CONNECTED IT WILL NOT | | | KINK. | | | | | | 4) DRY STANDPIPE IS TO BE PROPERLY | | | SUPPORTED WITH RISER CLAMPS TO ENSURE | | | STABILITY. | | | | | | 5) ALL UNDERGROUND AND ABOVEGROUND | | | PIPING IS TO BE PRESSURE TESTED IN | | | ACCORDANCE WITH NFPA 24. | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 659-8096,EXT.8497 | | | 835-2910 |
|