| Plan Review Notes For Permit 02050452 |
| Permit Number |
02050452 |
|
| Review Stop |
FS |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-05-28 00:00:00 | 1) PLEASE SHOW THE LOCATION OF THE | | | FIRE SPRINKLER, FIRE DEPARTMENT | | | CONNECTION AND THE LOCATION OF THE | | | FIRE HYDRANT USED TO SUPPORT THIS | | | DEVICE. PLEASE BE ADVISED THAT THE | | | FIRE DEPARTMENT CONNECTION IS TO BE | | | LOCATED NO FARTHER THAN 150 FEET FROM | | | IT. | | | | | | 2) IT WAS NOTED THAT CENTRAL FIRE | | | SPRINKLERS ARE PLANNED FOR USE. | | | PLEASE SEE WWW.SPRINKLERREPLACEMENT.COM | | | TO VERIFY THAT THE HEADS PLANNED FOR | | | USE ARE NOT ON THE VOLUNTARY RECALL | | | LIST. | | | | | | 3) PLEASE PROVIDE CUT SHEETS FOR | | | EQUIPMENT AND DEVICES PLANNED FOR | | | USE. | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 659-8096,EXT.8497 | | | 835-2910 |
|