| Plan Review Notes For Permit 02050448 |
| Permit Number |
02050448 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-05-14 00:00:00 | ~~~~~~~~~~~~~~~~UNSAT!~~~~~~~~~~~~~~~~~~ | | | | | | 1} PLEASE LIST THE REQ`D ARC | | | FAULT PROTECTED CIRCUITS ON PANEL | | | SCHEDULE. PER 210-12 | | | | | | 2} PLEASE SUBMIT AIC RATINGS FOR | | | ALL NEW EQUIPMENT BEING INSTALLED. | | | MAINS/PANELS/BREAKERS MUST BE RATED FOR | | | THE AVAILABLE FAULT CURRENT PER 110-9. | | | | | | 3} PLEASE LIST THE REQ`D BATH(S) | | | CIRCUIT(S). PER 210-11-C-3 | | | MUST BE 20A AND #12AWG,SHOWN ON PLANS. | | | | | | 4} LOCATION OF THE MAIN DISCONNECT DOES | | | NOT APPEAR ON THE HOUSE, ONLY ON THE | | | RISER DIAGRAM, PLEASE CLARIFY. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/659-8096 EXT. 8392 |
|