Plan Review Notes
Plan Review Notes For Permit 02050448
Permit Number 02050448
Review Stop E
Sequence Number 1
Notes
Date Text
2002-05-14 00:00:00~~~~~~~~~~~~~~~~UNSAT!~~~~~~~~~~~~~~~~~~
  
 1} PLEASE LIST THE REQ`D ARC
 FAULT PROTECTED CIRCUITS ON PANEL
 SCHEDULE. PER 210-12
  
 2} PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
  
 3} PLEASE LIST THE REQ`D BATH(S)
 CIRCUIT(S). PER 210-11-C-3
 MUST BE 20A AND #12AWG,SHOWN ON PLANS.
  
 4} LOCATION OF THE MAIN DISCONNECT DOES
 NOT APPEAR ON THE HOUSE, ONLY ON THE
 RISER DIAGRAM, PLEASE CLARIFY.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/659-8096 EXT. 8392