| Plan Review Notes For Permit 02050442 |
| Permit Number |
02050442 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-06-03 00:00:00 | DENIED: | | | | | | 1. EXHAUST AIR EQUALS 1000CFM AND | | | OUTSIDE AIR EQUALS 240 CFM WHICH HAS | | | THIS BUILDING APPARENTLY 760 CFM | | | NEGATIVE. PROVIDE INFORMATION ON WHERE | | | ADDITIONAL OUTSIDE IS FROM TO AVOID | | | NEGATIVE PRESSURE ON BUILDING. | | | | | | 2. FAN SHUT DOWN BY DUCT SMOKE DETECTOR | | | REQUIRED FOR AHU, WITH NOTIFICATION BY | | | BY BUILDING ALARM SYSTEM. | | | | | | 3. NOTE: AHU LOCATION SHALL BE IN | | | RESPECT TO BUILDING CONSTRUCTION TO | | | ALLOW FOR SERVICE AND REPLACEMENT OF | | | EQUIPMENT WITHOUT RESTRICTION OR | | | REMOVAL OF BUILDING COMPONENTS. |
|