2003-02-19 00:00:00*************** UNSAT ***************
  
 1)NOTE: PLEASE SEE NOTES FROM PREVIOUS
 REVIEWS AND NOTES REDLINED ON PLANS.
 PLANS SHOW 3 WATER HEATERS, PANEL SCHED-
 -ULES SHOW 2, AND LOAD CALCUALTIONS DO
 NOT CORRELATE WITH LOADS SHOWN ON PANEL
 SCHEDULES??
  
 2)NOTE: PLEASE CLARIFY NOTE ON A-3P,
 MENTIONS SWITCH TO BUNKER RANCH RD??
 PLEASE EXPLAIN?
  
 3)NOTE: PLEASE SEE FS/ FAC,471.025/
 481.221. PLANS MUST BE RE-PRINTED AND
 SIGNED DATED AND SEALED BY THE ARCH/
 ENGINEER OF RECORD. PLEASE NOTE, ALL
 HAND WRITTEN CHANGES ON PLANS NEED TO
 GO BACK TO ARCH FOR PRINTING.
 PLEASE ALSO ADDRESS NOTES ABOVE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESITONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372