2002-06-12 00:00:00 
 BUILDING PLAN REVIEW
 PERMIT: 02040434
 ADD: 5501 S. FLAGLER
 CONT: ROGER G THOMAS GEN CONT INC
 TEL: 575-1389
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 1) THE FINISHED FLOOR LEVEL SHALL BE
 VERIFIED BY A SIGNED AND SEALED
 ELEVATION CERTIFICATE REQUIRED, ELEVA-
 TION OF FIRST FLOOR, POOL PUMP SLAB &
 A/C CONDENSER SLAB TO BE ABOVE 7'-6".
 A-5 FLOOD ZONE, CITY CODE REQUIRES AN
 ADDITIONAL 6", OR 7'-6".
  
 2)FL BLDG 1909.3 (EXEPTION# 2)
 CONCRETE SLABS ON GRADE CONTAINING 6X6/
 W1.4XW1.4 WELDED WIRE REINFORCEMENT
 FABRIC LOCATED IN THE MIDDLE TO THE
 UPPER 1/3RD OF THE SLAB SHALL BE SUP-
 PORTED BY APPROVED MATERIALS OR SUPPORTS
 AT SPACING NOT TO EXCEED 3 FT OR IN
 ACCORDANCE WITH MANUFACTURER'S SPEC.
  
 3)FL. BLD CODE 1606.1.7 THE FOLLOWING
 INFORMATION RELATED TO WIND SHALL BE
 SHOWN ON THE CONSTRUCTION DRAWINGS,
 1)- BASIC WIND SPEED, MPH
 2)- WIND IMPORTANCE FACTOR, & BUILDING
 CATEGORY
 3)- WIND EXPOSURE
 4)- INTERNAL PRESSURE COEFFICIENT,
 5)- COMPONENTS & CLADDING, THE DESIGN
 WIND PRESSURES IN TERMS OF PSF.
  
 THIS INFORMATION IS TO BE ON THE DESIGN
 DOCUMENTS! PREASURE ZONES ON PLANS!
  
 4) FL BLD CODE CHAP 13 ENERGY EFFICENCY
 PROVIDE ENERGY CALS/ W MANUAL "J"
 THE MANUAL "J" PROVIDED BUT NOT FORM
 600A-2001, RESIDENTIAL WHOLE BUILDING
 PERFORMANCE METHOD A.
  
 5)1804.1.3 THE BOTTOM OF THE FOUNDA-
 TION SHALL EXTEND NO LESS THAN 12"
 BELOW FINISH GRADE.
  
 6) FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORT, SBCCI OR DADE COUNTY
 REPORT ARE ACCEPTED. MISSING REPORTS:
 A) CUSTOM ENTRY FRONT DOOR& FRAME
 SITE SPECIFIC ENGINEERING (PRODUCT
 APPROVAL) REQUIRES THE WET SIGNATURE,
 DATE AND EMBOSSED SEAL OF THE ENGINEER
 CERTIFYING THE PRODUCT AND OF THE DESIGN
 PROFESSIONAL OF RECORD.
 B) GARAGE OVERHEAD DOOR, HIGHLIGHT THE
 MANUFACTURER & MODEL.
 C)ROOFING REPORT, MISSING 7 PAGES.
  
 7) PROVIDE EMERGENCY EGRESS WINDOW IN
 SLEEPING ROOMS WITH A MINIMUM NET CLEAR
 OPENING HEIGHT OF 24INCHES,NET CLEAR
 OPENING WIDTH OF 20 INCHES AND NET CLEAR
 OPENING AREA OF 5.7 SQ.FT. GROUND FLOOR
 OPENINGS ARE PERMITTED TO HAVE A NET
 CLEAR OPENING OF 5.0 SQ.FT. SILL HEIGHT
 SHALL NOT BE MORE THAN 44 INCHES ABOVE
 THE FLOOR. 1997 SBC 1005.4
 THE WINDOW SCHEDULE LIST WINDOW"H"
 AS A PR 2'-0"X6'-0" CASEMENT WINDOW. THE
 REPORT PROVIDED LIST THE FRAME AS
 2.25", X2= 4.5"OR 19.5" LESS THE LIGHT
 AND FRAME.
  
 8)1707.4.5.1 MULLIONS OCCURRING
 BETWEEN INDIVIDUAL WINDOW AND GLASS
 DOOR ASSEMBLIES. TESTING REPORTS ARE
 REQUIRED BY AN APPROVED TESTING
 LABORATORY OR BE ENGINEERED. IDENTIFY
 WHICH MULLIONS ARE TO BE USED IN EACH
 CASE, EXAMPLE VETICAL WINDOW "H" A 1X3
 MULLION, AS PART OF THE WINDOW SCHEDULE.
 WINDOW INSTALLER MAY CHOOSE A MULION
 NOT SPECIFIED BY ARCHETECT.
  
 9) S-3ROOF FRAMING PLAN, MISSING THE
 MAGNITUDE,AND DIRECTION OF LOADS TO BE
 RESISTED. THE PLAN INDICATES THE USE OF
 HUGHES & SEMCO THEY HAVE BEEN OUT OF
 BUSINESS FOR 2 YEARS.PROVIDE MANUFACT-
 URER AND MODEL OF ANCHOR.
  
 10)-1707.3.1 JOIST HANGERS, FRAMING
 ANCHORS & SIMILAR DEVICES SHALL BE TEST-
 ED IN ACCORDANCE W/ ASTM D 1761 & BE
 LABELED AND LISTED FOR THEIR LOAD CARRY-
 ING CAPACITY.
  
 11) 2806.1.2. FACTORY BUILT FIREPLACES
 SHALL BE TESTED IN ACCORDANCE WITH AND
 MEET THE REQUIREMENTS OF UL 127. PROVIDE
 MANUFACTURERS SPEC.
  
 12) 2305.2.2 FLOOR/CEILING ASSEMBLIES
 SINGLE FAMILY DWELLINGS. IN FLOOR/CEIL/
 ING ASSEMBLIES SEPERATING USEABLE SPACE
 INTO 2 OR MORE APPROXIMATE AREAS WITH NO
 AREA GREATER THAN 500 SQ FT. DRAFTSTOP-
 PING SHALL BE PROVIDED PARALLEL TO THE
 MAIN FRAMING MEMBERS.
  
 13) 2305.1.4 (1) FIREBLOCKING SHALL BE
 INSTALLED IN WOOD FRAME CONSTRUCTION IN-
 CLUDDING FURRED SPACES AT CEILING &
 FLOOR LEVELS.
  
 IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
  
 LOOK FOR COMMENTS BY THE OTHER PLAN
 REVIEW DISCIPLINES THAT MAY BE WRITTEN
 ON THE APPLICATION, PLANS, OR ATTACHED
 SEPARATELY. WHEN RESUBMITTING PLANS
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A
 DESCRIPTION OF THE REVISION MADE, IDEN-
 TIFYING THE SHEET OR SPECIFICATION PAGE
 WHERE THE CHANGES CAN BE FOUND, WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION.
 JIM WITMER
 PLAN REVIEW
 TEL: (561)659-8096 EX.8412
 FAX: (561)659-8026