Plan Review Notes
Plan Review Notes For Permit 02050434
Permit Number 02050434
Review Stop E
Sequence Number 1
Notes
Date Text
2002-05-24 00:00:00**************** UNSAT ****************
  
 1) NOTE: PLEASE SHOW ALL OUTLETS SERVING
 KITCHEN COUNTERSPACE AS GFI/GFI PROTECT-
 -ED PER 210-8-A-6.
 INCLUDES KITCHEN ISLANDS.
  
 2)NOTE: PLEASE NOTE THAT ALL GARAGE AND
 BATHS OUTLETS ARE TO BE SHOWN AS GFI/GFI
 PROTECTED.210-8
  
 3)NOTE: PLEASE LIST THE REQ`D ARC FAULT
 PROTECTED OUTLETS ON PANEL SCHEDULE.
 PER 210-12
  
 4) NOTE: SMOKE DETECTORS ARE REQUIRED
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS.
 ALSO ON EACH LEVEL OF A MULTI-LEVEL
 DWELLING UNIT. ROOMS WITH BATHS AND OR
 CLOSETS ARE CONSIDERED SLEEPING ROOMS.
 PER NFPA-72 2-2.1.1.1.
 IN THE VICINITY OF BEDROOMS AND CLOSE
 PROXIMITY OF STIRWAYS. 2-5.2.1.3
 3'FT FROM BATHS/KITCHENS.2-5.2.1.6
  
 4)NOTE: PLEASE NOTE MISSING OUTLET FOR
 A/C EQUIPMENT. PER 210-63 AND/OR SECTION
 306 OF THE MECHANICAL CODE.
  
 5)NOTE: PLEASE NOTE MISSING EGRESS
 LIGHTING PER 210-70.
  
 6)NOTE: PLEASE NOTE THAT ALL A/C CU`S,
 AHU`S NEED TO BE SHOWN ON ELECTRICAL
 PLANS.
 PLEASE SHOW ALL REQ`D DISC`S PER 440-11
  
 7)NOTE: PLEASE NOTE A/C NOTES UNDER ELEC
 RISER MENTION 3-A/C SYSTEMS AND ONLY
 TWO ARE SHOWN ON PANEL SCHEDULES AND ON
 LOAD CALCULATIONS. PLEASE ALSO NOTE
 A/C LOAD NEED TO CORRELATE WITH PANEL
 SCHEDULES.
  
 8)NOTE: PLEASE NOTE MISSING EQUIPMENT
 GROUNDING CONDUCTOR BETWEEN MAIN DISC`S
 AND PANELS. SIZE PER 250-122
  
 9)NOTE: PLEASE NOTE SOME CLOSET LIGHTS
 SHOWN WHERE PROHIBITED PER 410-8.
  
 10)NOTE: PLEASE NOTE ELECTRICAL WATER
 HEATERS NOT SHOWN ON E-SHEETS.?DISC`S?
  
 11)NOTE: PLEASE NOTE THAT ALL ROOM
 DESIGNATIONS NEED TO BE SHOWN ON
 ELECTRICAL PLANS.
  
 12)NOTE: PLEASE NOTE KITCHEN COUNTER-
 LAYOUT AND OUTLETS SPACING NOT COMPLETE.
 210-52 C
 PLEASE CALRIFY SWICHES SHOWN AS GFI`S??
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372