| 2002-05-24 00:00:00 | **************** UNSAT **************** |
| | |
| | 1) NOTE: PLEASE SHOW ALL OUTLETS SERVING |
| | KITCHEN COUNTERSPACE AS GFI/GFI PROTECT- |
| | -ED PER 210-8-A-6. |
| | INCLUDES KITCHEN ISLANDS. |
| | |
| | 2)NOTE: PLEASE NOTE THAT ALL GARAGE AND |
| | BATHS OUTLETS ARE TO BE SHOWN AS GFI/GFI |
| | PROTECTED.210-8 |
| | |
| | 3)NOTE: PLEASE LIST THE REQ`D ARC FAULT |
| | PROTECTED OUTLETS ON PANEL SCHEDULE. |
| | PER 210-12 |
| | |
| | 4) NOTE: SMOKE DETECTORS ARE REQUIRED |
| | INSIDE AND OUTSIDE ALL SLEEPING ROOMS. |
| | ALSO ON EACH LEVEL OF A MULTI-LEVEL |
| | DWELLING UNIT. ROOMS WITH BATHS AND OR |
| | CLOSETS ARE CONSIDERED SLEEPING ROOMS. |
| | PER NFPA-72 2-2.1.1.1. |
| | IN THE VICINITY OF BEDROOMS AND CLOSE |
| | PROXIMITY OF STIRWAYS. 2-5.2.1.3 |
| | 3'FT FROM BATHS/KITCHENS.2-5.2.1.6 |
| | |
| | 4)NOTE: PLEASE NOTE MISSING OUTLET FOR |
| | A/C EQUIPMENT. PER 210-63 AND/OR SECTION |
| | 306 OF THE MECHANICAL CODE. |
| | |
| | 5)NOTE: PLEASE NOTE MISSING EGRESS |
| | LIGHTING PER 210-70. |
| | |
| | 6)NOTE: PLEASE NOTE THAT ALL A/C CU`S, |
| | AHU`S NEED TO BE SHOWN ON ELECTRICAL |
| | PLANS. |
| | PLEASE SHOW ALL REQ`D DISC`S PER 440-11 |
| | |
| | 7)NOTE: PLEASE NOTE A/C NOTES UNDER ELEC |
| | RISER MENTION 3-A/C SYSTEMS AND ONLY |
| | TWO ARE SHOWN ON PANEL SCHEDULES AND ON |
| | LOAD CALCULATIONS. PLEASE ALSO NOTE |
| | A/C LOAD NEED TO CORRELATE WITH PANEL |
| | SCHEDULES. |
| | |
| | 8)NOTE: PLEASE NOTE MISSING EQUIPMENT |
| | GROUNDING CONDUCTOR BETWEEN MAIN DISC`S |
| | AND PANELS. SIZE PER 250-122 |
| | |
| | 9)NOTE: PLEASE NOTE SOME CLOSET LIGHTS |
| | SHOWN WHERE PROHIBITED PER 410-8. |
| | |
| | 10)NOTE: PLEASE NOTE ELECTRICAL WATER |
| | HEATERS NOT SHOWN ON E-SHEETS.?DISC`S? |
| | |
| | 11)NOTE: PLEASE NOTE THAT ALL ROOM |
| | DESIGNATIONS NEED TO BE SHOWN ON |
| | ELECTRICAL PLANS. |
| | |
| | 12)NOTE: PLEASE NOTE KITCHEN COUNTER- |
| | LAYOUT AND OUTLETS SPACING NOT COMPLETE. |
| | 210-52 C |
| | PLEASE CALRIFY SWICHES SHOWN AS GFI`S?? |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-659-8096 EXT 8372 |