| Plan Review Notes For Permit 02050431 |
| Permit Number |
02050431 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-05-21 00:00:00 | ***************** UNSAT ************** | | | | | | 1)NOTE: PLEASE NOTE CIRCUITS ON RISER | | | FOR NEW 9,11,13,15 ARE COMING FROM A | | | 277/480 PANEL?? RECEPTS? 277V? | | | PLEASE CLARIFY. | | | | | | 2 )NOTE: PLEASE NOTE THAT THE LOAD | | | CALCULATIONS NEED TO BE SHOWN. SQ FT/ | | | RECEPT LOADS ETC. PER 220-3,220-10, | | | 220-11, 220-13. (215-5) | | | | | | 3) NOTE: PLEASE SHOW ALL CONTINUOUS AT | | | 125%. (LIGHTING ETC) | | | 215-2,215-3,230-42 | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|