| Plan Review Notes For Permit 02050381 |
| Permit Number |
02050381 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-05-23 00:00:00 | ************* UNSAT *************** | | | | | | 1)NOTE; PLEASE NOTE 4TH AND 7TH FLOORS | | | ARE REQ`D TO BE SEPARATE PERMITS! | | | SUBMIT NEW PERMIT APPLICATION FOR 7TH | | | FLOOR. | | | | | | 2)NOTE: PLEASE NOTE WRONG ELECTRICAL | | | CODE REFERENCED. WE ARE UNDER THE 99 NEC | | | NO FLORIDA ELECTRICAL CODE?? | | | | | | 3)NOTE: PLEASE NOTE THAT ALL BRANCH | | | CIRCUIT #`S NEED TO BE PLACED ON PLANS | | | AND CORRELATE WITH SUBMITTED PANEL | | | SCHEDULES. | | | | | | 4)NOTE: PLEASE PROVIDE NEW E-SHEETS FOR | | | 4TH FLR SET. THOSE PAGES WERE VOIDED. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|