| 2002-05-17 00:00:00 | PLEASE PROVIDE CURRENT TEST AND OR | | | NOTICE OF ACCEPTANCE REPORTS FOR THE | | | EXTERIOR GLAZED STORE FRONT SYSTEM | | | INTENDED TO BE INSTALLED WITH THIS | | | PERMIT.ALTERNATIVELY, A SEPARATE | | | PERMIT AND FEES WILL BE REQUIRED FOR | | | THE INSTALLATION. | | | | | | PROVIDE FOR THE EXTENSION OF THE FIRE | | | SPRINKLER SYSTEM TO THE PROPOSED | | | ENCLOSURE. | | | | | | THE EXISTING BUILDING IS OF TYPE V CONST | | | RUCTION AND IS REQUIRED BY FBC 607 TO HA | | | VE EXTERIOR WALLS OF NONCOMBUSTIBLE CONS | | | TRUCTION.SHEET A3 INDICATES THE USE OF | | | PLYWOOD SHEATHING.SEE FBC 1403.6.7. |
|