Plan Review Notes
Plan Review Notes For Permit 02050312
Permit Number 02050312
Review Stop B
Sequence Number 1
Notes
Date Text
2002-05-22 00:00:00THE ADDED FLOOR AREA IS SUBJECT TO
 IMPACT FEES COLLECTED BY THE COUNTY.
 THE PERMIT PLANS MUST BE STAMPED BY
 THAT OFFICE AND A COPY OF THE PAID
 RECEIPT ATTACHED TO THE PERMIT
 APPLICATION.
  
 PROVIDE MODIFICATION OF THE FIRE
 SPRINKLER SYSTEM FOR THIS TYPE OF
 STORAGE.
  
 THE STRUCTURAL FLOOR SYSTEM SHOULD BE
 DESIGNED BY A FLORIDA REGISTERED
 ENGINEER IN ACCORDANCE WITH THE FLORIDA
 BUILDING CODE.SHOW THE NECESSARY
 LOADING INFORMATION FOR THE "DECK BY
 OTHERS" AS TO THE LOCATION, MAGNITUDE,
 DIRECTION AND NATURE OF THE FORCES TO
 BE RESISTED.
  
 PROVIDE A NOTE THAT THE DESIGNER OF
 RECORD HAS REVIEWED THE PLANS FOR
 CONFORMANCE WITH THE ORIGINAL DESIGN.