| Notes |
| Date |
Text |
| 2002-11-06 00:00:00 | BUILDING PLAN REVIEW | | | PERMIT: 02050306 | | | ADD: 319 E LAKEWOOD | | | CONT: ROYAL PALM COLLECTION | | | TEL: (561)718-1135 | | | FL BLD CODE= 2001 FLORIDA BUILDING CODE | | | | | | REVISION: OCT 21/02***DENIED*** | | | | | | 1) NO PRODUCT TESTING REPORTS, | | | REQUIRED FOR WIND EVEN IF GLAZED OPEN- | | | INGS SHALL HAVE STORM SHUTTERS. | | | | | | 2) REVISION DOESN'T INDICATE ANY CUT | | | SECTIONS FOR CARRYING THE LOADS THAT | | | MUST BE TRANSFERRED OVER THE NEW OPEN- | | | INGS (HEADER, AMOUNT OF JACK STUDS & | | | FULL LENGTH STUDS REQUIRED @ EACH OPEN- | | | ING. NO INDICATION AS TO HOLD DOWN | | | DEVICES NOR STRAPPING REQUIREMENTS. | | | BUILDING PLAN REVIEW | | | JIM WITMER |
|