2002-06-24 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
  
 1) SANITARY RISER DIAGRAM S/1 DOES NOT
 MEET CODE. TOILET ROOM FROM 2ND FLOOR
 CAN NOT DRAIN INTO THE BATHROOM GROUP OF
 THE FIRST FLOOR. 1ST FLOOR BATH FLOOR
 PLAN SHOWS A W/C, LAV, AND A SHOWER. BUT
 THE RISER SHOWS 4 FIXTURES. SHOWER IN
 2ND FLOOR BATH NOT VENTED.
 2) SANITARY RISER DIAGRAM S/2 TUB NOT
 VENTED AND A 3" VTR IS REQUIRED.
 3) SANITARY RISER DIAGRAM S/3 HORIZONTAL
 DRY VENT IS NOT APPROVED.
  
 PLEASE SEE ATTACHED SHEET FOR COMPLIANCE
  