| 2002-07-17 00:00:00 | SECOND CHECKLIST: |
| | 1-ARCHITECT DIDN'T ADDRESSED ITEM #3 |
| | FROM PREVIOUS CHECKLIST DATED 6-13-02. |
| | NEW SHEET HAS AREAS CLOUDED BUT THERE |
| | WERE NOT CHANGES DONE. SEE COMMENTS |
| | ON SHEET #7 AND PLEASE RETURN MARKED |
| | SHEET TO EXPEDITE REVIEW PROCESS. |
| | 2-FOUNDATION PLAN: ARCHITECT RESPONDED |
| | TO COMMENT REGARDING CONCRETE SLAB |
| | JOINTS BY CITING THE CODE SECTION. |
| | NEED SPECIFIC INFORMATION. CITING THE |
| | CODE IS NOT ALLOWED. SECTION 104.2.1 |
| | CITY AMENDMENTS TO FBC 2001. |
| | **NOTE: IF ARCHITECT WANTS TO USE THE |
| | EXCEPTION FOR NOT DESIGNING CONTROL |
| | JOINTS, THEN SPECIFY THE SUPPORTS FOR |
| | THE WWM. SEE SECTION 1909.3 FBC 2001. |
| | 3-PROVIDE PRODUCT APPROVALS FOR DOORS & |
| | WINDOWS ASSEMBLIES AS SHOWN ON PLANS. |
| | **NOTE: CONTRACTOR (NEIL) SAID HE IS |
| | GETTING TOGETHER THE SITE SPECIFIC |
| | PRODUCT APPROVALS. |
| | 4-STORM SHUTTERS: |
| | A)REVISE KEY PLAN AND ANCHOR SCHEDULE |
| | TO MATCH PLANS (SEE COMMENTS ONSTORM |
| | SHUTTERS PACKAGE SUBMITTED). |
| | B)CLEARLY INDICATE ON SHUTTER'S DWGS |
| | SPECIFIC MOUNTING CONDITIONS & ANCHORS |
| | TO BE USED. |
| | **IF INFORMATION IS NOT COMPLETE AT TIME |
| | OF RESUBMITTAL, THEN A SEPARATE PERMIT |
| | MAY BE APPLIED FOR BY SUBCONTRACTOR. |
| | |
| | |
| | NOTES: |
| | *THESE COMMENTS APPLY TO LOTS 7 AND 8. |
| | *DRAWINGS & COMMENTS TO BE FILED UNDER |
| | PERMIT #02050254. |