| 2002-05-15 00:00:00 | BUILDING PLAN REVIEW | | | PROVISO | | | 02050217/ 700 NORTHPOINT PKWY/ 500 | | | | | | THE PLANS DO NOT INDICATE ANY PENETRA- | | | TIONS OF FIRE RATED WALLS NOR HORIZONTAL | | | ASSEMBLIES (FLOORS). IF PENETRATIONS ARE | | | REQUIRED, SUBMITTAL FOR THROUGH PENETRA- | | | TIONS FOR FIRE RATED WALLS SHALL COMPLY | | | WITH 705.5.1.1OR 705.5.1.2. | | | PENETRATIONS THROUGH HORIZONTAL ASSEM- | | | BLIES SHALL COMPLY WITH 705.6.1.1 OR | | | ANY QUESTIONS PLEASE CALL, | | | JIM WITMER | | | BUILDING PLAN REVIEW | | | DEPARTMENT OF CONSTRUCTION SERVICES | | | CITY OF WEST PALM BEACH | | | (561) 659-8096 EXT. 8412 |
|