| Plan Review Notes For Permit 02050208 |
| Permit Number |
02050208 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-05-27 00:00:00 | PASS/PROVISO | | | 1) NEED REVISED PLAN FOR FINAL | | | INSPECTION | | | 2) VARIFY TYPE OF VENTILATION USED FOR | | | FRESH AIR NATURAL 402 OR MECHANICAL | | | 403 | | | 3) NEED CALCULATIONS FOR TYPE OF | | | VENTILATION USED | | | 4) FOR BATH EXHAUST REFER TO SECTION 403 | | | MECHANICAL VENTILATION NO WINDOW | | | EXECPTION | | | 5) CAN NOT PENETRATE O LOT LINE WALL | | | WITH DRYER VENT | | | 6) MISSING DUCT SIZE,GRILL SIZE,CFM | | | ON TWO DROPS | | | 7) NEED FAN SHUTDOWN AT FINAL INSPECTION | | | PLAN REVIEW BY HAROLD MOSER | | | (561)659-8096 EXT 9390 |
|