| Plan Review Notes For Permit 02050166 |
| Permit Number |
02050166 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-05-06 00:00:00 | PROVISO: | | | | | | CONDENSATE SHALL DISCHARGE A MINIMUM OF | | | 12" AWAY FROM THE BUILDING STRUCTURE AS | | | PER 2001 FBC 1503.4.4. | | | | | | BALANCED AIR RETURN REQUIRED - PRESSURE | | | DIFFERENTIALS ACROSS CLOSED DOORS WHERE | | | RETURNS ARE CENTERALLY LOCATED SHALL BE | | | LIMITED TO .001" WC OR LESS.PROVIDE | | | AIR DUCT PATHWAYS OR AIR TRANSFER PATH- | | | WAYS FROM HIGH PRESSURE ZONE TO LOW | | | ZONE. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|