Plan Review Notes
Plan Review Notes For Permit 02050144
Permit Number 02050144
Review Stop P
Sequence Number 3
Notes
Date Text
2002-08-29 00:00:00DENIED
 REFERENCE: FBC-2001 CHAPTER 11
 FBC-2001 PLUMBING
  
 1) SHT A4-2 PLEASE PROVIDE DETAILS FOR
 BACKING IN ADAPTABLE TOILET ROOM #332.
 SEE SECTION 11-4.26.3(2)(3)(4). ALSO
 SHOW THE GUAGE OF THE GALVANIZED SHEET
 METAL.
 2) SHT A4-2 W/C SHALL BE 18" OFF WALL.
 3) SHT A4-2 LAV SHALL BE 15" OFF WALL &
 CABINETS SHALL BE REMOVABLE FOR CLEAR
 FLOOR SPACE OR 2' OFF WALL AND PARALLEL
 APPROACH. HEIGHT SHALL BE 34"
 4) SHT P2-1 MANUFACTURE INFORMATION NOT
 SUBMITTED SHOWING NSF APPROVAL. (SEE #6
 FROM PREVIOUS REVIEW)
 5) SHT P1-3 BACKFLOW ON WATER SERVICE
 SHALL BE MAXIMUM OF 4'0" OFF FLOOR FOR
 SERVICE AND SHALL DRAIN INTO A FLOOR
 SINK OR OTHER ACCEPTABLE RECEPTICLE.
 6) SHT P1-3 WATER HAMMER ARRESTORS SHALL
 BE LOCATED NEAR THE FIXTURES IN AN EFF-
 ECTIVE RANGE" NOT AT THE TOP OF THE DROP
 OR ON THE MAIN ABOVE THE CEILING. (SEE
 #10 FROM PREVIOUS REVIEW)
 7) FROM PREVIOUS REVIEW, FIXTURE UNITS
 FOR RISERS TO BE SHOWN ON SANITARY RISER
 DIAGRAM. SHOW ACCUMULATED DFU'S IN SYS-
 TEM.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377