| Notes |
| Date |
Text |
| 2002-08-29 00:00:00 | DENIED | | | REFERENCE: FBC-2001 CHAPTER 11 | | | FBC-2001 PLUMBING | | | | | | 1) SHT A4-2 PLEASE PROVIDE DETAILS FOR | | | BACKING IN ADAPTABLE TOILET ROOM #332. | | | SEE SECTION 11-4.26.3(2)(3)(4). ALSO | | | SHOW THE GUAGE OF THE GALVANIZED SHEET | | | METAL. | | | 2) SHT A4-2 W/C SHALL BE 18" OFF WALL. | | | 3) SHT A4-2 LAV SHALL BE 15" OFF WALL & | | | CABINETS SHALL BE REMOVABLE FOR CLEAR | | | FLOOR SPACE OR 2' OFF WALL AND PARALLEL | | | APPROACH. HEIGHT SHALL BE 34" | | | 4) SHT P2-1 MANUFACTURE INFORMATION NOT | | | SUBMITTED SHOWING NSF APPROVAL. (SEE #6 | | | FROM PREVIOUS REVIEW) | | | 5) SHT P1-3 BACKFLOW ON WATER SERVICE | | | SHALL BE MAXIMUM OF 4'0" OFF FLOOR FOR | | | SERVICE AND SHALL DRAIN INTO A FLOOR | | | SINK OR OTHER ACCEPTABLE RECEPTICLE. | | | 6) SHT P1-3 WATER HAMMER ARRESTORS SHALL | | | BE LOCATED NEAR THE FIXTURES IN AN EFF- | | | ECTIVE RANGE" NOT AT THE TOP OF THE DROP | | | OR ON THE MAIN ABOVE THE CEILING. (SEE | | | #10 FROM PREVIOUS REVIEW) | | | 7) FROM PREVIOUS REVIEW, FIXTURE UNITS | | | FOR RISERS TO BE SHOWN ON SANITARY RISER | | | DIAGRAM. SHOW ACCUMULATED DFU'S IN SYS- | | | TEM. | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 |
|