2002-08-29 00:00:00PROVISO;
  
 IF EQUIPMENT FAN CAPACITY CAN EXCEED
 2000CFM OR IF AIR IS INTERMIXED WHERE
 SEVERAL UNITS COMBINED IS GREATER THAN
 2000 CFM FAN SHUT DOWN BY DUCT SMOKE
 DETECTOR WILL BE REQUIRED.
 PROVIDE EQUIPMENT MANUFACTURES
 INFORMATION SHOWING THAT THE EQUIPMENT
 CAN UNDER NO CONFIGURATION PRODUCE
 GREATER THAN 20000CFM FOR THE 5 TON
 UNITS PRIOR TO FINAL.