| Plan Review Notes For Permit 02050144 |
| Permit Number |
02050144 |
|
| Review Stop |
M |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2002-08-29 00:00:00 | PROVISO; | | | | | | IF EQUIPMENT FAN CAPACITY CAN EXCEED | | | 2000CFM OR IF AIR IS INTERMIXED WHERE | | | SEVERAL UNITS COMBINED IS GREATER THAN | | | 2000 CFM FAN SHUT DOWN BY DUCT SMOKE | | | DETECTOR WILL BE REQUIRED. | | | PROVIDE EQUIPMENT MANUFACTURES | | | INFORMATION SHOWING THAT THE EQUIPMENT | | | CAN UNDER NO CONFIGURATION PRODUCE | | | GREATER THAN 20000CFM FOR THE 5 TON | | | UNITS PRIOR TO FINAL. |
|